Fast delivery within 72 Hours
B&R X67AI4850
4 inputs for potentiometer displacement gauge
The module is a 4-channel analog input module. It is used to evaluate potentiometer displacement gauges.
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
4 inputs for potentiometer displacement gauge
The module is a 4-channel analog input module. It is used to evaluate potentiometer displacement gauges.
Specification
| I/O module | 4 inputs for potentiometer displacement gauge |
|---|---|
| B&R ID code | 0x9957 |
| Status indicators | Channel status, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Input | Yes, using LED status indicator and software |
| X2X Link | M12, B-coded |
| Inputs | 4x M12, A-coded |
| I/O power supply | M8, 4-pin |
| Bus | 0.75 W |
| Internal I/O | 2 W |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 – Max. 60°C TÜV 05 ATEX 7201X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| KC | Yes |
| Nominal voltage | 24 VDC |
| Voltage range | 18 to 30 VDC |
| Integrated protective function | Reverse polarity protection |
| Short-circuit proof | Yes |
| Potentiometer supply voltage Upot | 4.5 V / Max. 50 mA |
| Voltage drop for short-circuit protection at 50 mA | Max. 0.13 VDC |
| Input type | Single-ended input in the range of 0 to Upot |
| Digital converter resolution | 15-bit |
| Measurement sensor | 0.5 to 10 kΩ, potentiometer |
| Conversion time | <200 µs for all channels |
| Output format | INT (16-bit 2s complement) |
| Short-circuit protection Upot | Yes |
| Influence of cable length | Twisted and shielded conductors, cable length as short as possible, cable routing separate from load circuits, without intermediate terminal to sensor |
| Common-mode range | 0 to Upot |
| Insulation voltage between input and bus | 500 Veff |
| Quantization; LSB value (14-bit) | 275 µV |
| Conversion procedure | Sample & Hold |
| Open circuit on GND | 0x7FFF |
| Open circuit on slider | 0x7FFF |
| Open circuit on Upot | 0x0000 |
| Valid range of values | 0x0000 – 0x7FFF |
| Cutoff frequency | 10 kHz |
| Slope | 60 dB/Dec. |
| Electrical isolation | Bus isolated from analog input |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP67 |
| Operation | -25 to 60°C |
| Derating | – |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Width | 53 mm |
| Height | 85 mm |
| Depth | 42 mm |
| Weight | 195 g |
| M8 | Max. 0.4 Nm |
| M12 | Max. 0.6 Nm |