B&R X20cCP1301
Intel x86 200 MHz compatible with integrated I/O processorOnboard Ethernet and USB1 slot for modular interface expansion30 digital inputs/outputs and 2 analog inputs integrated in the device1 GB onboa…
Shipping & Delivery
- 
Courier delivery
 
Our courier will deliver to the specified address
2-3 Days
From $20
- 
DHL Courier delivery
 
DHL courier will deliver to the specified address
2-3 Days
From $40
- 
Warranty 1 year
 
- 
Free 30-Day returns
 
Description
Intel x86 200 MHz compatible with integrated I/O processorOnboard Ethernet and USB1 slot for modular interface expansion30 digital inputs/outputs and 2 analog inputs integrated in the device1 GB onboard flash drive128 MB DDR3 SDRAMFanlessNo batteryBacked-up real-time clock
The X20 Compact controller series is characterized by 3 integrated I/O modules. The device is equipped with 30 different digital inputs/outputs and 2 analog inputs. 1 analog input can be used for Pt1000 resistance temperature measurement. The X20CP1301 is equipped with an Intel x86 200 MHz compatible processor, 128 MB RAM and 1 GB built-in flash drive. The FRAM for storing remanent variables has 16 kB available. A fanless and battery-free design ensures maintenance-free operation. The controller is equipped with one Ethernet, one USB and one RS232 interface. Various bus and network systems can be flexibly integrated into the X20 system via a freely usable slot for X20 communication modules.
Specification
| Interfaces | 
 1x RS232, 1x Ethernet, 1x USB, 1x X2X Link  | 
|---|---|
| System module | 
 Controller  | 
| B&R ID code | 
 0xEB58  | 
| Cooling | 
 Fanless  | 
| Status indicators | 
 CPU function, Ethernet, RS232, PLC power supply, I/O power supply, I/O function per channel  | 
| Outputs | 
 Digital outputs: Yes, using LED status indicator and software (output error status)  | 
| CPU function | 
 Yes, using LED status indicator  | 
| RS232 data transfer | 
 Yes, using LED status indicator  | 
| Inputs | 
 Analog inputs: Yes, using LED status indicator and software  | 
| Ethernet | 
 Yes, using LED status indicator  | 
| I/O power supply | 
 Yes, using LED status indicator  | 
| Supply voltage monitoring | 
 Yes, using LED status indicator  | 
| Temperature | 
 Yes, using software register  | 
| Controller redundancy | 
 No  | 
| ACOPOS support | 
 Yes  | 
| ReACTION-capable I/O channels | 
 No  | 
| Visual Components support | 
 Yes  | 
| Power consumption without interface module and USB | 
 4.3 W  | 
| Power consumption for X2X Link power supply | 
 0.8 W  | 
| Internal I/O | 
 2.3 W  | 
| Additional power dissipation caused by actuators (resistive) [W] | 
 –  | 
| Type of signal lines | 
 Shielded lines must be used for all high-speed digital inputs/outputs, line length: Max. 20 m  | 
| CE | 
 Yes  | 
| UKCA | 
 Yes  | 
| CRA (Cyber Resilience Act) | 
 Evaluation ongoing  | 
| ATEX | 
 Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZĂš 09 ATEX 0083X  | 
| UL | 
 cULus E115267Industrial control equipment  | 
| HazLoc | 
 cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5  | 
| DNV | 
 Temperature: B (0 to 55°C)Humidity: B (up to 100%)Vibration: B (4 g)EMC: B (bridge and open deck)  | 
| LR | 
 ENV1  | 
| KR | 
 Yes  | 
| ABS | 
 Yes  | 
| BV | 
 EC33BTemperature: 5 – 55°CVibration: 4 gEMC: Bridge and open deck  | 
| Input voltage | 
 24 VDC -15% / +20%  | 
| Input current | 
 Max. 1 A  | 
| Fuse | 
 Required line fuse: Max. 10 A, slow-blow  | 
| Reverse polarity protection | 
 Yes  | 
| Nominal output power | 
 2 W  | 
| Parallel connection | 
 Yes  | 
| Redundant operation | 
 Yes  | 
| Nominal output voltage | 
 24 VDC  | 
| Permissible contact load | 
 10 A  | 
| Real-time clock | 
 Retention for at least 300 hours, typ. 1000 hours at 25°C, 1 s resolution, -18 to 28 ppm accuracy at 25°C  | 
| FPU | 
 Yes  | 
| Type | 
 USB 1.1/2.0  | 
| Clock frequency | 
 200 MHz  | 
| Data code | 
 16 kB  | 
| Program code | 
 16 kB  | 
| L2 cache | 
 128 kB  | 
| Integrated I/O processor | 
 Processes I/O data points in the background  | 
| Modular interface slots | 
 1  | 
| Remanent variables | 
 16 kB FRAM, retention >10 years  | 
| Shortest task class cycle time | 
 2 ms  | 
| Typical instruction cycle time | 
 0.0419 µs  | 
| RAM | 
 128 MB DDR3 SDRAM  | 
| Data retention | 
 10 years  | 
| Guaranteed | 
 40 TB  | 
| Results for 5 years | 
 21.9 GB/day  | 
| Guaranteed erase/write cycles | 
 20,000  | 
| Error-correcting code (ECC) | 
 Yes  | 
| Signal | 
 Ethernet  | 
| Variant | 
 Standard outputs and mixed channels: Current-sourcing FETHigh-speed outputs: Push-Pull  | 
| Max. distance | 
 900 m  | 
| Transfer rate | 
 10/100 Mbit/s  | 
| Line length | 
 Max. 100 m between 2 stations (segment length)  | 
| Physical layer | 
 10BASE-T/100BASE-TX  | 
| Half-duplex | 
 Yes  | 
| Full-duplex | 
 Yes  | 
| Autonegotiation | 
 Yes  | 
| Auto-MDI/MDIX | 
 Yes  | 
| Max. output current | 
 0.5 A  | 
| Fieldbus | 
 X2X Link master  | 
| Quantity | 
 4 standard outputs, 4 high-speed outputs and 4 mixed channels, configuration as input or output using software  | 
| Nominal voltage | 
 24 VDC  | 
| Input current at 24 VDC | 
 X1 – Standard inputs: Typ. 3.5 mAX2 – Standard inputs: Typ. 2.68 mAX2 – High-speed inputs: Typ. 3.5 mAX3 – Mixed channels: Typ. 2.68 mA  | 
| Input circuit | 
 Sink  | 
| Hardware | 
 Standard inputs and mixed channels: ≤200 μsHigh-speed inputs: ≤2 μs, when used as standard inputs: ≤200 μs  | 
| Software | 
 Default 1 ms, configurable between 0 and 25 ms in 0.1 ms increments  | 
| Connection type | 
 1-wire connections  | 
| Input resistance | 
 X1 – Standard inputs: 6.8 kΩX2 – Standard inputs: 8.9 kΩX2 – High-speed inputs: 6.8 kΩX3 – Mixed channels: 8.9 kΩ  | 
| Additional functions | 
 X2 – High-speed digital inputs:2x 250 kHz event counting, 2x AB counter, ABR incremental encoder, direction/frequency, period measurement, gate measurement, differential time measurement, edge counters, edge times  | 
| Low | 
 <5 VDC  | 
| High | 
 >15 VDC  | 
| Encoder inputs | 
 24 V, asymmetrical  | 
| Counter size | 
 32-bit  | 
| Input frequency | 
 Max. 10 kHz  | 
| Evaluation | 
 1x  | 
| Encoder power supply | 
 Module-internal, max. 300 mA  | 
| Overload characteristics of encoder power supply | 
 Short-circuit proof, overload-proof  | 
| Signal form | 
 Square wave pulse  | 
| Counter frequency | 
 250 kHz  | 
| Possible measurements | 
 Period measurement, gate measurement, differential time measurement, edge counter, edge times  | 
| Measurements per module | 
 Each function up to 2x  | 
| Timestamp | 
 1 µs resolution  | 
| Input | 
 Resistance measurement with constant current supply for 2-wire connections  | 
| Input type | 
 Differential input  | 
| Voltage | 
 <0.025%  | 
| Current | 
 <0.05%  | 
| Conversion time | 
 Only temperature input enabled: 200 µsTemperature and analog input enabled: 400 µs  | 
| Data type | 
 INT  | 
| Input protection | 
 Protection against wiring with supply voltage  | 
| Output of digital value during overload | 
 Configurable  | 
| Conversion procedure | 
 SAR  | 
| Input filter | 
 First-order low-pass filter / cutoff frequency 7 Hz  | 
| Gain | 
 0.3% (Rev. <C0: 1.93%)  | 
| Offset | 
 0.15% (Rev. <C0: 0.32%)  | 
| DC | 
 70 dB  | 
| 50 Hz | 
 >60 dB  | 
| Common-mode range | 
 1 V  | 
| Crosstalk between channels | 
 <-70 dB  | 
| Digital converter resolution | 
 13-bit  | 
| Output format | 
 INT or UINT for resistance measurement  | 
| Pt1000 | 
 -200 to 850°C  | 
| Resistance measurement range | 
 0.1 to 4000 Ω  | 
| Temperature sensor resolution | 
 1 LSB = 0x0005 = 0.16°C  | 
| Resistance measurement resolution | 
 1 LSB = 0x0005 = 0.49 Ω  | 
| Sensor standard | 
 EN 60751  | 
| Linearization method | 
 Internal  | 
| Measuring current | 
 1 mA  | 
| Permissible input signal | 
 Short-term max. ±30 V  | 
| Max. gain drift | 
 0.023 %/°C  | 
| Max. offset drift | 
 0.012%/°C  | 
| Nonlinearity | 
 <0.05%  | 
| Standardized range of values for resistance measurement | 
 0.1 to 4000.0 Ω  | 
| Switching voltage | 
 24 VDC -15% / +20%  | 
| Nominal output current | 
 Standard outputs and mixed channels: 0.5 AHigh-speed outputs: 0.2 A  | 
| Total nominal current | 
 Standard outputs and mixed channels: 4 AHigh-speed outputs: 0.8 A  | 
| Output circuit | 
 Standard outputs and mixed channels: SourceHigh-speed outputs: Sink or source  | 
| Output protection | 
 Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current")Internal freewheeling diode for switching inductive loads (see section "Switching inductive loads")  | 
| Period duration | 
 5 to 65535 µs corresponds to 200 kHz to 15 Hz  | 
| Pulse duration | 
 0 to 100%, minimum 2.5 µs  | 
| Resolution for pulse duration | 
 0.1% of the configured frequency  | 
| Diagnostic status | 
 Standard outputs and mixed channels: Output monitoring with 10 ms delayHigh-speed outputs: Output monitoring with 10 µs delay  | 
| Leakage current when the output is switched off | 
 Standard outputs and mixed channels: 5 µAHigh-speed outputs: 25 µA  | 
| RDS(on) | 
 140 mΩ  | 
| Residual voltage | 
 Standard outputs and mixed channels: <0.1 V at nominal current 0.5 AHigh-speed outputs: <0.9 V at nominal current 0.1 A  | 
| Peak short-circuit current | 
 Standard outputs and mixed channels: <3 AHigh-speed outputs: <20 A  | 
| Switch-on in the event of overload shutdown or short-circuit shutdown | 
 Standard outputs and mixed channels: Approx. 10 ms (depends on module temperature)High-speed outputs: No switch-on  | 
| 0 → 1 | 
 Standard outputs and mixed channels: <300 µsHigh-speed outputs: <3 µs  | 
| 1 → 0 | 
 Standard outputs and mixed channels: <300 µsHigh-speed outputs: <3 µs  | 
| Resistive load | 
 Standard outputs and mixed channels: Max. 500 HzHigh-speed outputs: 50 kHz, max. 200 kHz (see section "Switching frequency derating for high-speed digital outputs")  | 
| Inductive load | 
 See section "Switching inductive loads".  | 
| Braking voltage when switching off inductive loads | 
 Standard outputs and mixed channels: Typ. 45 VDC  | 
| Electrical isolation | 
 Ethernet (IF2) and X2X (IF6) isolated from each other, from other interfaces and from PLCChannel isolated from busChannel not isolated from channel or PLC  | 
| Horizontal | 
 Yes  | 
| Vertical | 
 Yes  | 
| 0 to 2000 m | 
 No limitation  | 
| >2000 m | 
 Reduction of ambient temperature by 0.5°C per 100 m  | 
| Degree of protection per EN 60529 | 
 IP20  | 
| Horizontal mounting orientation | 
 -25 to 60°C  | 
| Vertical mounting orientation | 
 -25 to 50°C  | 
| Derating | 
 See section "Switching frequency derating for high-speed digital outputs".  | 
| Storage | 
 5 to 95%, non-condensing  | 
| Transport | 
 5 to 95%, non-condensing  | 
| Operation | 
 Up to 100%, condensing  | 
| Note | 
 X20 end cover plate (right) included in delivery3 X20 terminal blocks (16-pin) included in deliveryInterface module slot cover included in delivery  | 
| Width | 
 164 mm  | 
| Height | 
 99 mm  | 
| Depth | 
 75 mm  | 
| Weight | 
 300 g  | 
	
	
				
				
		
		
		
		
		
		
		