Fast delivery within 72 Hours
B&R 8I86T400300.00-000
Base device for ACOPOSinverter P86, 3x 380 to 480 V, 3.0 kW, EMC filter and brake chopper.Order number – ACOPOSinverter P86:8I86T400300.0P-100: Inverter with POWERLINK communication card
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
Base device for ACOPOSinverter P86, 3x 380 to 480 V, 3.0 kW, EMC filter and brake chopper.Order number – ACOPOSinverter P86:8I86T400300.0P-100: Inverter with POWERLINK communication card
Specification
| CE | Yes |
|---|---|
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| UL | cULus E225616 Power conversion equipment |
| Specified on nameplate | 3 kW (4 HP) |
| Mains input voltage | 3x 380 VAC -15% to 480 VAC +10% |
| Frequency | 50 to 60 Hz ±5% |
| Apparent power (at 480 VAC) | 7.1 kVA |
| Max. assumed short-circuit current (Isc) (short-circuit current at connection point) | 5 kA |
| Inrush current | Max. 36.1 A |
| At 380 VAC | 10.7 A |
| At 480 VAC | 8.5 A |
| External cooling | 112 W |
| Integrated EMC filter | Yes |
| Motor cable length per IEC/EN 61800-3 Cat. C2 environment 1 (public power network) | C2 level at 4 kHz with 50 m cable |
| Motor cable length per IEC/EN 61800-3 Cat. C3 environment 2 (industrial power system) | C3 level at 4 kHz with 100 m cable |
| With add-on filter | 8I0FT025.200-1 |
| Motor cable length per IEC/EN 61800-3 Cat. C1 environment 1 (public power network) | – |
| Nominal output current | 7.2 A |
| At nominal clock frequency (4 kHz or 2.5 kHz with higher inverter power) | No derating (up to 50°C) |
| Other clock frequencies | The derating curves are included in the installation instructions, which can be downloaded from www.br-automation.com. |
| Starting at 1000 m above sea level | 1%, per 100 m |
| Max. transient current for 60 s | 11 A |
| Max. transient current for 2 s | 13 A |
| Output frequency range | 0.1 to 599 Hz |
| Nominal clock frequency | 4 kHz |
| Min. | 2 kHz |
| Max. | 16 kHz |
| Shielded cable | 100 m |
| Non-shielded cable | 100 m |
| Induction motor | Sensorless vector control: 1. Voltage controlled with constant torque → Default mode 2. Voltage controlled with variable torque → Energy-saving mode, e.g. for fans and pumps Vector control with encoder: 1. Current-controlled with constant torque → Default mode Sensorless slip control: 1. With V/f characteristic curve for constant torque → Default mode 2. With V/f characteristic curve for constant torque (up to 6 f ranges) → Mode for individual special applications 3. With V/f characteristic curve for quadratically increasing torque → Energy-saving mode, e.g. for fans and pumps |
| Synchronous motor | Sensorless vector control: 1. Voltage controlled with constant torque → Default mode Vector control with encoder: 1. Current-controlled with constant torque → Default mode |
| Main protective functions of inverter | Thermal protection against power stage overheating Protection against short circuits between motor phases, overcurrent between output phases and ground, overvoltages on the DC bus, exceeding the speed limit. Safety function for: Overvoltage and undervoltage of the mains supply, mains phase failure with 3-phase power supply |
| Integrated dynamic brake transistors | Yes |
| Min. resistance value (external) | 31 Ω |
| Input voltage | 24 VDC (min. 20.4 VDC, max. 27 VDC) |
| Current | 500 Ω |
| Output voltage 24 VDC | 24 VDC (min. 20.4 VDC, max. 27 VDC) |
| Max. output current at 24 VDC | Max. 200 mA |
| Output voltage 10 VDC | 10.5 VDC ±5% |
| Max. output current at 10 VDC | Max. 10 mA |
| Type | Type 3 |
| Quantity | 1 |
| Nominal voltage | 30 VDC / 250 VAC |
| Input circuit | Source |
| Low | <0.6 V |
| High | >2.5 V |
| Input - ACOPOSinverter | Yes |
| Input - Input | No |
| Sampling time | 5 ms ±1 ms |
| Input impedance | 2.2 kΩ |
| Input frequency | 0 to 30 kHz |
| Nonlinearity | ±0.2% |
| Basic accuracy | ±1% with temperature fluctuation of 60°C |
| Voltage | 470 Ω |
| Resolution | 10-bit |
| Max. voltage | 30 VDC |
| Output circuit | Source or sink |
| Max. current | 100 mA |
| Switching current range | Min. switching current: 5 mA at 24 VDC Max. switching current: R1: At cos φ = 1: Max. 3 A / At cos φ = 0.4: Max. 2 A R2: At cos φ = 1: Max. 5 A / At cos φ = 0.4: Max. 2 A |
| Relay 1 | 1 changeover contact |
| Relay 2 | 1 normally open contact |
| Output - ACOPOSinverter | Yes |
| Output - Output | No |
| Response time (max.) | 5 ms ±0.5 ms |
| Output | 0 to 10 VDC or 0 to 20 mA |
| Power dissipation relative to continuous apparent power | IE2 (10, 25): 1% (3x 380 VAC), 0.8% (3x 480 VAC) IE2 (50, 25): 0.9% (3x 380 VAC), 0.8% (3x 480 VAC) IE2 (10, 50): 1.2% (3x 380 VAC), 1% (3x 480 VAC) IE2 (50, 50): 1.2% (3x 380 VAC), 1% (3x 480 VAC) IE2 (90, 50): 1.3% (3x 380 VAC), 1.1% (3x 480 VAC) IE2 (10, 100): 1.8% (3x 380 VAC), 1.4% (3x 480 VAC) IE2 (50, 100): 1.7% (3x 380 VAC), 1.5% (3x 480 VAC) IE2 (90, 100): 2.1% (3x 380 VAC), 1.8% (3x 480 VAC) |
| Nominal losses in standby mode | 15 W (3x 380 VAC), 16 W (3x 480 VAC) |
| Degree of protection per EN 61800-5-1 | IP20 |
| Degree of protection per EN 60529 | IP20 |
| Max. relative humidity per EN/IEC 60721-3-3 class 3K3 | 5 to 95%, non-condensing |
| Maximum installation elevation | ≤1000 m without derating 1000 to 3000 m with Derating |
| Max. pollution degree per IEC/EN 61800-5-1 | 2 (non-conductive pollution) |
| Ambient conditions per IEC 60721-3-3 | Class 3C3 and 3S3 |
| Operating position | Vertical mounting orientation ±10° |
| Operation | -15 to 50°C without derating 50 to 60°C with derating |
| Storage | -40 to 70°C |
| Max. vibration resistance | 1 gn 9 to 200 Hz EN/IEC 60721-3-3 class 3M3 1.5 mm peak to peak 2 to 19 Hz EN/IEC 60721-3-3 class 3M3 |
| Max. shock resistance | 15 gn (duration = 11 ms) per EN/IEC 60721-3-3 class 3M3 |
| Width | 85 mm |
| Height | 270 mm |
| Depth | 232.5 mm |
| Weight | 2.2 kg |
Customer Reviews
Rated 0 out of 5
0 reviews
Rated 5 out of 5
0
Rated 4 out of 5
0
Rated 3 out of 5
0
Rated 2 out of 5
0
Rated 1 out of 5
0
Be the first to review “B&R 8I86T400300.00-000” Cancel reply

Reviews
Clear filtersThere are no reviews yet.