Fast delivery within 72 Hours

Wago 857-560

Short description:WAGO’s voltage signal conditioner measures AC/DC voltages up to 300 V, converting the input signal into a standard analog signal at the output.Features:Two isolated measurement input…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Short description:WAGO’s voltage signal conditioner measures AC/DC voltages up to 300 V, converting the input signal into a standard analog signal at the output.Features:Two isolated measurement inputs for 30 and 300 V AC/DCRMS measurement or arithmetic mean valueA digital signal output reacts to configured measurement range limits (on/off switching delay and threshold value switch function can be configured with up to two threshold values).Switchable filter function3-way electrical isolation with 2.5 kV test voltage

Specification

Technical data - Configuration

Configuration optionsDIP switch, WAGO Interface Configuration Software

Technical data - Input

Input signal typeVoltage
Input signal (voltage)300 V AC/DC (IN 1), 30 V AC/DC (IN 2)
Measurement frequency10 … 100 Hz (AC)
Frequency range10 … 100 Hz (AC)
Input resistance (voltage input)≥ 300 kΩ
Response threshold300 mV (IN 1); 30 mV (IN 2)
Resolution (voltage)30 mV (IN 1), 3 mV (IN 2)

Technical data - Output (analog)

Output signal typeCurrent, Voltage
Output signal (voltage)0 … 5 V, 1 … 5 V, 0 … 10 V, 2 … 10 V (invertible, also bipolar)
Output signal (current)0 … 10 mA, 2 … 10 mA, 0 … 20 mA, 4 … 20 mA (invertable, also bipolar)
Load impedance (voltage output)≥ 1 kΩ
Load impedance (current output)≤ 600 Ω

Technical data - Output (digital)

Switching voltage (DO) max.Supply voltage applied
Continuous current (DO) max.100 mA (no internal restriction)
Number of switching thresholds (DO)1 or 2 (adjustable)
Configurable rise/fall delay time (DO)0 … 60 s (via software)

Technical data - Signal processing

Measurement methodRMS measurement; Arithmetic mean value
Limit frequency2 kHz
Software filter (adjustable)Moving average value (filter level: 30)
Step response (typ.)30 ms

Technical data - Measurement error

Transmission error (max.)≤ 0.5 % (of the full scale value)
Temperature coefficient≤ 0.01 %/K

Technical data - Power supply

Power supply type24 VDC
Nominal supply voltage U<sub>S</sub>24 VDC
Supply voltage range±30 %
Current consumption at nominal supply voltage≤ 46 mA (+ IDO)

Safety and protection

Rated voltage300 V; 150 V (UL)
Measurement category per EN/UL 61010-2-030CAT II (input)
Note on insulation parametersDanger: Configuration via the service interface must only be performed with a voltage-free measurement input! The digital output (DO) operates at the supply potential.
Protection typeIP20

Safety and protection - Test voltage

Test voltage (input/analog output/supply/service interface)2.5 kVAC; 50 … 60 Hz; 1 min

Safety and protection - Insulation coordination (UL)

Overvoltage categoryII
Pollution degree2
Insulation type (input/analog output/supply/service interface)Reinforced insulation (safe isolation)

Safety and protection - Insulation coordination

Overvoltage categoryII
Pollution degree2
Insulation type (input/analog output/supply/service interface)Double insulation (impedance and basic insulation);Requirement: The GND 1 input must not become hazardous when active and the measurement is performed as a low-side measurement!

Connection data

Connection technologyPush-in CAGE CLAMP®
Solid conductor0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor0.34 … 2.5 mm² / 22 … 14 AWG
Strip length9 … 10 mm / 0.35 … 0.39 inches

Physical data

Width6 mm / 0.236 inches
Height94 mm / 3.701 inches
Depth from upper-edge of DIN-rail97.8 mm / 3.85 inches

Mechanical data

Mounting typeDIN-35 rail

Material data

Insulation material (main housing)Polyamide (PA66)
Flammability class per UL94V0
Fire load0.013 MJ
Weight34 g

Environmental requirements

Ambient temperature (operation)-40 … +70 °C (at nominal current)
Ambient temperature (storage)-40 … +85 °C
Temperature range of connection cable≥ (Tambient + 10 K)
Temperature range of the connection cable (UL)80 °C
Relative humidity5 … 95 % (no condensation permissible)
Operating altitude (max.)2000 m

Standards and specifications

Conformity markingCE
EMC immunity to interferenceEN 61000-6-2; EN 61326-2-3; EN 50121-3-2
EMC emission of interferenceEN 61000-6-3; EN 61326-2-3; EN 50121-3-2
Standards/specificationsEN 61010-1, EN 61373, EN 50121-3-2

Commercial data

PU (SPU)1 pcs
Packaging typebag
Country of originDE
GTIN4055143481571
Customs tariff number85437090300

Product Classification

UNSPSC41113630
eCl@ss 10.027-21-01-25
eCl@ss 9.027-21-01-25
ETIM 9.0EC002477
ETIM 10.0EC002477
ECCNNO US CLASSIFICATION

Environmental Product Compliance

CAS-No.11120-22-2, 1303-86-2, 1317-36-8, 7439-92-1, 75980-60-8
REACH Candidate List SubstanceDiboron trioxide, Lead, Lead monoxide, Lead silicate, Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)-
RoHS Compliance StatusCompliant,With Exemption
RoHS Exemption6(c), 7(a), 7(c)-I, 7(c)-II
SCIP notification number (Austria)e39ffb15-f554-4816-a577-82f294898011
SCIP notification number (Belgium)4e3c29de-9839-4487-8450-21e290cce428
SCIP notification number (Bulgaria)a62309da-6e93-49d0-9ca6-31ee2cbbee05
SCIP notification number (Czech Republic)4e179792-6d82-43e7-a0bc-61c1bbf5190b
SCIP notification number (Denmark)d9e51cec-dd28-4094-8511-04bde8b72d54
SCIP notification number (Finland)bfe296bd-7c71-4597-9172-90001c8c8f8c
SCIP notification number (France)396a94fe-cc62-47b3-ae66-2fa168881435
SCIP notification number (Germany)fbcf3bd8-1c98-48b5-a7db-5e8e81acb7f1
SCIP notification number (Hungary)2b23d5cf-8881-40dc-b708-8ad82f781d25
SCIP notification number (Italy)a6a805df-791f-45bb-b670-7af08d995145
SCIP notification number (Netherlands)9cd592c7-c51d-4742-a863-2d13dd0e889c
SCIP notification number (Poland)2b299cf8-7127-49b5-ba48-13995ec4bfb6
SCIP notification number (Romania)d8ac266d-97e5-40de-a3e4-c13eda02beb5
SCIP notification number (Sweden)02e70fdd-434e-4d94-91a6-1e9375b034c3

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Wago 857-560”