PID Temperature Adjustment Unit (Multi-input 4-channel). KV-TF40. Series: Programmable Logic Controller. Series code: KV-X series

Specification

Model NamePID Temperature Adjustment Unit (Multi-input 4-channel)
Model CodeKV-TF40
Series TitleProgrammable Logic Controller
Series CodeKV-X series
Data Sheet URLhttps://www.keyence.com/download/download/confirmation/?dlSeriesId=WS_157158&dlModelId=PM_084TF40&dlSiteId=1&dlLanguageId=en-US&dlLangType=en-US
CAD URLhttps://www.keyence.com/products/controls/plc-building-block-type/kv-x/downloads/?mode=cd&modelId=PM_084TF40
Manuals URLhttps://www.keyence.com/products/controls/plc-building-block-type/kv-x/downloads/?mode=ma&modelId=PM_084TF40
ModelKV-TF40
TypeTemperature control unit
Memory elementsEEPROM rewritable one million times
Number of temperature input points4 ch
InputThermocoupler/Platinum temperature measuring resistor*1
Temperature sensor typesThermocoupler: K, J, T, E, R, B, N, S, W5Re/W26RePlatinum temperature measuring resistor: JPt100, Pt100
Indicated accuracy±0.3% of F.S. ±1 digit (at 25°C 77°F), ±0.7% of F.S. ±1 digit (at 0 to 50°C 32 to 122°F)
Cold junction correction precision±1°C ±1.8°F
Sampling cycle125 ms/ch (500 ms/4 ch)
Control period1 to 100 seconds
Operation modePID control (with auto-tuning and 3 mode stabilizer function installed),Heat/cool PID control (with auto-tuning and 3 mode stabilizer function installed), ON/OFF control
Tuning modePID auto-tuning mode
Control outputTransistor (sink)
Alarm outputTransistor (sink)*2
Alarm modeAbsolute value upper limit, absolute value lower limit, deviation upper limit, deviation lower limit, deviation upper limit unexcited,deviation lower limit unexcited, deviation upper and lower limits, within upper and lower limit deviation, absolute value upper limit unexcited, absolute value lower limit unexcited*3
Output - Rated load30 VDC, 100 mA or less
Output - Leakage current at OFF100 μA or less
Output - Residual voltage at ON1.5 V or less
Current sensor (CT) input4 ch*4
Current measurement precisionLarger of ±5% of an input value and ±2 A of an input value
Insulation modeBetween inputs and outputs: Photocoupler and transformer insulation, Between input channels: Photocoupler and transformer insulation
OthersHeater wire breaking alarm, control loop wire breaking alarm, measured valuebias, output limit, slope setup, manual reset, output control when an error occurs
Internal current consumption210 mA or less
WeightApprox. 270 g