Fast delivery within 72 Hours

B&R X90AT910.04-00

9 to 32 VDC4 current, voltage, temperature or digital inputs or PWM outputsTemperature measurementX2X LinkThe AT option board offers 4 additional channels that can be used for current, voltage or temp…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

9 to 32 VDC4 current, voltage, temperature or digital inputs or PWM outputsTemperature measurementX2X LinkThe AT option board offers 4 additional channels that can be used for current, voltage or temperature measurement. It is also possible to use the analog inputs as PWM signal outputs or digital inputs (with toggling between sink mode and source mode). Communication to the mainboard is made possible via X2X Link.

Specification

I/O module4 inputs for Pt1000 resistance temperature measurement, analog inputs, PWM signal outputs, 1-wire connections
B&R ID code0xEC23
Status indicators
Power consumption0.6 W
Digital - DigitalNo
Digital - AnalogNo
UN ECE-R10Yes
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Quantity0 to 4, depends on the use of multifunction inputs/outputs
FunctionsResistance measurement input Pt1000, digital input, sink/source circuit, analog input 0 to 10 V, 0 to 32 V, 0 to 20 mA, PWM signal output high-side, configurable per channel
Input voltage9 to 32 VDC
Input current at 24 VDCTyp. 2.4 mA
Input circuitSink/Source, configurable
Hardware500 μs at switching threshold = 50% supply voltage
SoftwareFilter level configurable in software
Input resistance10 kΩ
Input delay<0.5 ms (at 200 μs sampling rate)
Switching thresholdFixed or ratiometric, configurable
Input0 to 10 V / 0 to 32 V or 0 to 20 mA
Digital converter resolution12-bit
Conversion time200 μs for all channels
Data typeINT
Voltage0.2%
Current0.2%
Open-circuit detectionFrom the application
Reverse polarity protectionYes
Nominal0 to 10 V / 0 to 32 V or 0 to 20 mA
Max. error at 25°C<1%
Crosstalk between channels-70 dB
Cutoff frequency230 Hz
Slope40 dB
Filter timeConfigurable
Output formatINT
Temperature-800 to 2700, 0.1°C increments
Resistance0 to 2000, 1 Ω increments
SensorPt1000
Temperature measurement range-80 to 270°C
Resistance measurement range0 to 2000 Ω
Temperature sensor resolution1 LSB <0.5°C
Resistance measurement resolution1 LSB <2 Ω
Linearization methodInternal
Measuring currentMax. 1.7 mA (temperature measurement) Max. 2.3 mA (resistance measurement)
Reference1980 Ω ±0.1%
Permissible input signalMax. 32 V
Max. gain drift0.015%/°C
Max. offset drift0.009%/°C
Nonlinearity<0.25%
Nominal voltage12 / 24 VDC
Switching voltage9 to 32 V
Voltage dropMax. 3.5 V
Nominal current10 mA
0 → 1<1 µs
1 → 0<1 µs
Resistive loadMax. 1 kHz
Output circuitSource
Output protectionThermal current limiting at 50 mA on short circuit
VariantHigh-side FET
Leakage current when the output is switched off<5 μA
Residual voltage<2.5 V at 10 mA nominal current
Peak short-circuit current250 mA
AnyYes
Degree of protection per EN 60529Up to IP69K
Horizontal mounting orientation-40 to 85°C housing surface
Vertical mounting orientation-40 to 85°C housing surface
Storage5 to 100%, condensing
Transport5 to 100%, condensing
Operation5 to 100%, condensing
Width47 mm
Length95 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X90AT910.04-00”