8 safe digital inputs, sink circuit2 pulse outputs – available on all 4 female connectors2 standard inputs, sink circuit2 standard outputs, source circuitDevice supplySoftware input filter configurabl…

3 in stock

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

8 safe digital inputs, sink circuit2 pulse outputs – available on all 4 female connectors2 standard inputs, sink circuit2 standard outputs, source circuitDevice supplySoftware input filter configurable for each channelStandardized 8-pin M12 device interface

This module is equipped with 8 safe digital inputs. They are designed for a nominal voltage of 24 VDC.The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3.The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.

Specification

I/O module2x M12 interface each with 2 safe type A digital inputs and 2 pulse outputs, 24 VDC,2x standardized 8-pin M12 device interface each with 1 digital input without safety function and 2 safe type A digital inputs and 2 pulse outputs, 24 VDC and 1 digital output without safety function, 24 VDC, 0.6 A and 1 device power supply, 24 VDC, 2 A
B&R ID code0xBB7C
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
I/O functionYes, using LED status indicator and software
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time1 ms
Inputs/OutputsM12 8-pin or M12 5-pin, A-coded
I/O power supplyM8, 4-pin
Bus0.9 W
Internal I/O2.1 W
Digital outputs0.216
Pulse outputs0.192
Channel - BusYes
Channel - ChannelNo
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA IIA T5 GcIP67, Ta = 0 – Max. 60°CTÜV 05 ATEX 7201X
ULcULus E115267Industrial control equipment
HazLoccCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5
KCYes
NoteSee section “Safety characteristics”.
Output voltage24 VDC -15% / +20%
Output current2 A
Nominal voltage24 VDC
Voltage range18 to 30 VDC
Integrated protective functionReverse polarity protection
Quantity8
Input characteristics per EN 61131-2Type 1
Input voltage24 VDC -15% / +20%
Input current at 24 VDCMin. 2 mA to max. 8.28 mA
Input circuitSink
Hardware≤150 μs
Input resistanceMin. 2.9 kΩ
Low<5 VDC
High>15 VDC
Insulation voltage between channel and bus500 Veff
VariantPush-Pull
SoftwareConfigurable between 0 and 500 ms
Error detection time200 ms
Line length between signal source (pulse output or external signal) and inputMax. 60 m with unshielded lineMax. 400 m with shielded line
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section “Inrush current behavior for output channels”.
Nominal output current40 mA
Total nominal current80 mA
Output protectionShutdown of individual channels in the event of overload or short circuit
Leakage current when the output is switched off0.1 mA
RDS(on)60 Ω
Peak short-circuit current25 A for 15 µs
Braking voltage when switching off inductive loads50 VDC
Max. capacitive load100 nF
Peak output current1 A
Short-circuit current100 mAeff
AnyYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP67
Operation-40 to 60°C
Storage-40 to 85°C
Transport-40 to 85°C
Width53 mm
Height85 mm
Depth42 mm
Weight190 g
M8Max. 0.4 Nm
M12Max. 0.6 Nm