Fast delivery within 72 Hours
B&R X67AT1322
4 inputs for resistance temperature measurementPT100, PT1000 and other resistance temperature sensorsDirect resistance measurementConfigurable sensor type per channel2-wire and 4-wire measurement…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
4 inputs for resistance temperature measurementPT100, PT1000 and other resistance temperature sensorsDirect resistance measurementConfigurable sensor type per channel2-wire and 4-wire measurement
The module is a temperature module for KTY10, KTY84, Pt100 and Pt1000 resistance temperature sensors. The sensors can be connected with 2-wire or 4-wire connections. The sensor type can be set selectively for each input.
Specification
| I/O module |
4 inputs for KTY10-6, KTY84-130, Pt100 or Pt1000 resistance temperature measurement |
|---|---|
| B&R ID code |
0x1488 |
| Status indicators |
I/O function per channel, supply voltage, bus function |
| Inputs |
4x M12, A-coded |
| I/O power supply |
M8, 4-pin |
| X2X Link |
M12, B-coded |
| Internal I/O |
1.5 W |
| X2X Link power supply |
0.75 W |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA IIA T5 GcIP67, Ta = 0 – Max. 60°CTÜV 05 ATEX 7201X |
| UL |
cULus E115267Industrial control equipment |
| HazLoc |
cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| KC |
Yes |
| Nominal voltage |
24 VDC |
| Voltage range |
18 to 30 VDC |
| Integrated protective function |
Reverse polarity protection |
| Input |
Resistance measurement with constant current supply for 2- or 4-wire connections |
| Digital converter resolution |
16-bit |
| Filter time |
Configurable between 2 and 20 ms |
| Same sensor types |
75 ms per channel with 50 Hz filter |
| When switching sensor type |
195 ms per channel with 50 Hz filter |
| Conversion procedure |
Sigma-delta |
| Output format |
INT or UINT for resistance measurement |
| Sensor type |
Configurable per channel |
| KTY10-6 |
1 LSB = 0.1°C |
| KTY84-130 |
1 LSB = 0.1°C |
| Pt100 |
1 LSB = 0.1°C |
| Pt1000 |
1 LSB = 0.1°C |
| Resistance measurement range |
0.1 to 4500 Ω / 0.05 to 2250 Ω |
| Sensor standard |
EN 60751 |
| Common-mode range |
±1 VDC |
| Insulation voltage between channel and bus |
500 Veff |
| Linearization method |
Software |
| Measuring current |
250 µA ±1.25% |
| Reference |
4530 Ω ±0.1% |
| Permissible input signal |
Short-term max. ±30 V |
| Gain |
0.01% |
| Offset |
0.015% |
| Max. gain drift |
0.003 %/°C |
| Max. offset drift |
5.25 mΩ/°C |
| Nonlinearity |
<0.002% |
| Crosstalk between channels |
<-70 dB |
| G = 1 |
1 LSB = Typ. 69.1223 mΩ ±0.1% |
| G = 2 |
1 LSB = Typ. 34.5611 mΩ ±0.1% |
| Cutoff frequency |
115 Hz / First-order filter |
| Slope |
-20 dB |
| 50 Hz |
>70 dB |
| DC |
>70 dB |
| Range undershoot |
0x0000 |
| Range overshoot |
0xFFFF |
| Open circuit |
0xFFFF |
| General fault |
0xFFFF |
| Open inputs |
0xFFFF |
| Electrical isolation |
Channel isolated from busChannel not isolated from channel |
| Any |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP67 |
| Operation |
-25 to 60°C |
| Derating |
– |
| Storage |
-40 to 85°C |
| Transport |
-40 to 85°C |
| Width |
53 mm |
| Height |
85 mm |
| Depth |
42 mm |
| Weight |
200 g |
| M8 |
Max. 0.4 Nm |
| M12 |
Max. 0.6 Nm |

Reviews