Fast delivery within 72 Hours
B&R X20cDO4633
4 digital outputsOutputs with integrated snubber circuitOutputs with 48 to 240 VACL switchingZero-crossing detectionPhase-angle controlOpen-circuit detection for each channelNegative half-waves can be…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
4 digital outputsOutputs with integrated snubber circuitOutputs with 48 to 240 VACL switchingZero-crossing detectionPhase-angle controlOpen-circuit detection for each channelNegative half-waves can be switched off50 Hz or 60 Hz2-wire connections240 V codingOSP modeFrequency mode
The module is a digital output module with phase-angle control that is equipped with 4 Triac outputs using 2-line connections. The supply (L and N) is fed directly to the module.
Specification
| I/O module | 4 digital outputs 48 to 240 VAC for 2-wire connections |
|---|---|
| B&R ID code | 0xE67D |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Outputs | Yes, using LED status indicator |
| Bus | 0.6 W |
| Internal I/O | – |
| External I/O | – |
| Additional power dissipation caused by actuators (resistive) [W] | +6.4 |
| CE | Yes |
| UKCA | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Variant | Triac |
| Circuit | L-switching |
| Nominal voltage | 48 to 240 VAC |
| Max. voltage | 264 VAC |
| Rated frequency | 47 to 63 Hz |
| Nominal output current | 1 A |
| Total nominal current | 4 A |
| Output current | 1.25 A |
| Summation current | 5 A |
| Connection type | 2-wire connections |
| Zero-crossing detection | Yes |
| Minimum holding current IH | 15 mA |
| Leakage current | Max. 2 mA at 240 V at 50 Hz Max. 2.4 mA at 240 V at 60 Hz |
| Residual voltage (on-state voltage) | 1.6 V |
| Area | 5 to 95% |
| Resolution | 1% |
| Accuracy (60 to 240 VAC) | <100 μs |
| Voltage monitoring L - N | No |
| Additional functions | Open-circuit detection |
| Overvoltage protection between L and N | Yes |
| Channel - Bus | Tested at 1500 VAC |
| Channel - Internal I/O | Tested at 2000 VAC |
| Channel - Ground | Tested at 1500 VAC |
| External | See section “External fuses”. |
| Internal | Snubber circuit (RC element) and varistor |
| Electrical isolation | Channel isolated from bus and I/O power supply |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Not permitted |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | See section “Derating”. |
| Starting temperature | Yes, -40°C |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Note | Order 1x terminal block X20TB32 separately. Order 1x bus module X20cBM32 separately. |
| Pitch | 25+0.2 mm |