B&R X20cCM0985-1
Energy measurement for 120 to 480 VACSimultaneous measurement of 2 AC mains networks plus 2 additional voltagesFor multifunctional measurement tasksIntelligent mains synchronization unit…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
Energy measurement for 120 to 480 VACSimultaneous measurement of 2 AC mains networks plus 2 additional voltagesFor multifunctional measurement tasksIntelligent mains synchronization unit
The module has a compact size and combines a power measurement module that has special features with a synchronization unit that is able to meet all demands.The measurement unit’s 3 current inputs are suitable for both X: 1 A and X: 5 A current transformers. Overcurrent resistance and the high resolution of the measurement unit round off its features. For the voltage inputs, the value range can be configured between 480 VAC and 120 VAC. The area of use includes 4-wire AC networks with a phase voltage up to 480 VAC and 3-wire systems, whereas L2 can be grounded (V-connection). The module can also handle Aron measuring circuits. The resulting measured values include the pure phase current; line-to-line voltage or phase voltage; the effective, reactive and apparent power parts; the mains frequency; the power factor and much more. In addition, peak values and energy meters are stored on the module in nonvolatile memory. Depending on the configuration, it is also possible to use a digital output as a pulse encoder for an external energy meter. The synchronization unit doesn’t just take the phasing and phase voltage into consideration; integrated intelligence also monitors the rate of change and other parameters, allowing them to influence when the synchronization output is switched. It is also possible to monitor a generator using a large number of additional conditions. A total of 4 voltage inputs provide substantial overall flexibility. Monitoring functions expand the features of the module. Dependent overcurrent monitoring is included, which utilizes the thermal capacity of the motor/generator to allow short overloads while still providing full protection. The dependent, delayed imbalanced load monitoring used to protect three-phase generator and three-phase networks from imbalanced load can be adapted to the characteristics of different generator types using parameters while taking their special thermal time constants into account.
Specification
| I/O module |
X20 energy measurement and synchronization module |
|---|---|
| B&R ID code |
0xE4FF |
| Status indicators |
Channel status, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Analog inputs |
Yes, using LED status indicator (measurement range of analog inputs) |
| Digital outputs |
Yes, using LED status indicator and software |
| Overvoltage category |
ll |
| Measurement range |
15.2 Hz to 2x nominal frequency |
| Accuracy |
<10 mHz at 400 V ±5% or 100 V ±5% |
| Bus |
1.05 W |
| Internal I/O |
4 W |
| Additional power dissipation caused by actuators (resistive) [W] |
– |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| DNV |
Temperature: B (0 to 55°C) |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| BV |
EC33B |
| Quantity |
1 |
| Variant |
Relay / Changeover contact |
| Nominal voltage |
30 VDC / 240 VAC |
| Switching voltage |
Max. 60 VDC / 250 VAC |
| Nominal output current |
1 A at 30 VDC / 1 A at 240 VAC |
| Total nominal current |
0.5 A |
| Connection type |
1-wire connections |
| Output circuit |
Source |
| Output protection |
Thermal shutdown in the event of overcurrent or short circuit |
| Diagnostic status |
Output monitoring with 10 ms delay |
| Leakage current when the output is switched off |
5 μA |
| Residual voltage |
<0.3 V at 0.1 A nominal current |
| Peak short-circuit current |
<2 A |
| Switch-on in the event of overload shutdown or short-circuit shutdown |
Approx. 10 ms, depends on the module temperature |
| 0 → 1 |
≤10 ms |
| 1 → 0 |
≤10 ms |
| Resistive load |
Max. 100 Hz |
| Insulation voltage between channel and bus |
500 Veff |
| Rated frequency |
DC / 45 to 63 Hz |
| Min. |
10 mA / 5 VDC |
| Max. |
30 W / 240 VAC |
| Actuator power supply |
External |
| Mechanical |
Min. 10 x 106 ops. |
| Electrical |
Min. 60 x 103 ops. (NC) at 1 A |
| Contact resistance |
Max. 100 mΩ |
| Internal |
None |
| External |
None |
| DC |
Inverse diode, RC combination or VDR |
| AC |
RC combination or VDR |
| Channel - Channel |
1000 VAC / 1 min |
| Channel - Bus |
4000 VAC / 1 min |
| Channels |
3 |
| Input |
1 A / 5 A AC |
| Input type |
Isolated current transformer according to the compensation principle with a magnetic sensor, for connecting an external transformer |
| Digital converter resolution |
±15-bit |
| 50 Hz |
10 ms |
| 60 Hz |
8.33 ms |
| Permissible input signal |
Max. 1.5 A / 7.7 A |
| ±120 VAC |
1 LSB = 0x0001 = 5.707 mV |
| ±480 VAC |
1 LSB = 0x0001 = 22.787 mV |
| Overshoot |
0x7FFF |
| Undershoot |
0x8001 |
| Conversion method |
SAR |
| Cutoff frequency |
10 kHz |
| Slope |
60 dB |
| Maximum gain drift |
0.07% per °C |
| Maximum offset drift |
Measurement range 2 A: 0.0064% per °C, measurement range 10 A: 0.00384% per °C |
| Crosstalk between channels |
-70 dB |
| Nonlinearity |
≤0.5% at 45 to 65 Hz |
| Protection against electric shock |
Protective impedance per EN 61131-2 |
| Test voltage between channel and bus (type test) |
3700 Veff |
| Output format |
INT |
| Input impedance in signal range |
Approx. 3 MΩ |
| Gain |
0.2% |
| Offset |
0.05% |
| Input protection |
Overvoltage protection |
| ±1 A |
1 LSB = 0x0001 = 189.903 μA |
| ±5 A |
1 LSB = 0x0001 = 949.513 μA |
| Thermal overcurrent |
15 x INom for 0.2 s |
| Monitored overcurrent |
4 x INom |
| Measurement range 1 A |
Max. 30 mΩ |
| Measurement range 5 A |
Max. 10 mΩ |
| Electrical isolation |
Bus isolated from I/O power supply and digital inputs and outputs Digital inputs and outputs isolated from each other |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
See section "Derating". |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
Up to 100%, condensing |
| Note |
Order 2x terminal block X20TB12 separately. |
| Pitch |
87.5+0.2 mm |