B&R X20cBT9100
X2X Link bus transmitterFor seamless expansion of the systemUp to 100 m segment lengthSupply for internal I/O power supplyOperation only on the rightmost slot…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
X2X Link bus transmitterFor seamless expansion of the systemUp to 100 m segment lengthSupply for internal I/O power supplyOperation only on the rightmost slot
The bus transmitter is used for seamless expansion of the X20 system. Stations can be up to 100 m apart.The bus transmitter module is only permitted to be operated with a bus module where the internal I/O power supply is connected through (e.g. X20BM11). If the supply is used for the internal I/O power supply, this potential group is not permitted to be supplied by any other module. An I/O module with bus module X20BM01 must be used to isolate the potential group.
Specification
| Bus transmitter | X2X Link bus transmitter with supply for I/O |
|---|---|
| B&R ID code | 0xE219 |
| Status indicators | X2X bus function, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| X2X bus function | Yes, using LED status indicator |
| Bus | 0.5 W |
| As bus transmitter | 0.1 W |
| Additionally as supply module | 0.6 W |
| Additional power dissipation caused by actuators (resistive) [W] | – |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user’s manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Input voltage | 24 VDC -15% / +20% |
| Fuse | Required line fuse: Max. 10 A, slow-blow |
| Reverse polarity protection | No |
| Nominal output voltage | 24 VDC |
| Behavior on short circuit | Required line fuse |
| Permissible contact load | 10 A |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | – |
| Starting temperature | Yes, -40°C |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Note | Order 1x terminal block X20TB06 or X20TB12 separately. Order 1x bus module X20cBM11 separately. |
| Pitch | 12.5+0.2 mm |