Fast delivery within 72 Hours

B&R X20cBR9300

X2X Link bus receiverFeed for X2X Link and internal I/O supplyElectrical isolation of feed and X2X Link supplyRedundancy of X2X Link supply possible by operating multiple supply modules simultaneously…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

X2X Link bus receiverFeed for X2X Link and internal I/O supplyElectrical isolation of feed and X2X Link supplyRedundancy of X2X Link supply possible by operating multiple supply modules simultaneouslyOperation only on the slot to the far left

The bus receiver is used to connect the X20 System to the X2X Link. The module is equipped with a feed for the X2X Link as well as the internal I/O supply.

Specification

Bus receiver

X2X Link bus receiver with supply for I/O and bus

B&R ID code

0xDD48

Status indicators

X2X bus function, overload, operating state, module status

Module run/error

Yes, using LED status indicator and software

Overload

Yes, using LED status indicator and software

X2X bus function

Yes, using LED status indicator

Internal I/O

0.6 W

Additional power dissipation caused by actuators (resistive) [W]

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X

UL

cULus E115267Industrial control equipment

HazLoc

cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5

Input voltage

24 VDC -15% / +20%

Input current

Max. 0.7 A

Fuse

Required line fuse: Max. 10 A, slow-blow

Reverse polarity protection

No

Nominal output power

7 W

Parallel connection

Yes

Redundant operation

Yes

Overload characteristics

Short-circuit proof, temporary overload

Nominal output voltage

24 VDC

Behavior on short circuit

Required line fuse

Permissible contact load

10 A

Electrical isolation

X2X Link supply isolated from X2X Link power supplyI/O supply not isolated from I/O power supply

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

See section "Derating".

Starting temperature

Yes, -40°C

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

Up to 100%, condensing

Note

Order 1x terminal block X20TB12 separately.Order 1x power supply bus module X20cBM01 separately

Pitch