Fast delivery within 72 Hours

B&R X20cAT4222

4 inputs for resistance temperature measurementFor PT100 and PT1000Configurable sensor type per channelDirect resistance measurementConfigurable 2- or 3- wire connections per moduleConfigurable filter…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 inputs for resistance temperature measurementFor PT100 and PT1000Configurable sensor type per channelDirect resistance measurementConfigurable 2- or 3- wire connections per moduleConfigurable filter time

The module is equipped with 4 inputs for PT100/PT1000 resistance temperature measurement.

Specification

I/O module4 inputs for Pt100 or Pt1000 resistance temperature measurement
B&R ID code0xE215
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
Bus0.01 W
Internal I/O1.1 W
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
LRENV1
KRYes
ABSYes
BVEC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck
InputResistance measurement with constant current supply for 2- or 3-wire connections
Digital converter resolution16-bit
Filter timeConfigurable between 1 ms and 66.7 ms
1 channel20 ms with 50 Hz filter
2 - 4 channels40 ms per channel with 50 Hz filter
Conversion procedureSigma-delta
Output formatINT or UINT for resistance measurement
Sensor typeConfigurable per channel
Pt100-200.0 to 850.0°C
Pt1000-200.0 to 850.0°C
Resistance measurement range0.1 to 4500 Ω / 0.05 to 2250 Ω
Input filterFirst-order low-pass filter / cutoff frequency 500 Hz
Sensor standardEN 60751
Common-mode range>0.7 V
Insulation voltage between channel and bus500 Veff
Linearization methodInternal
Measuring current250 µA ±1.25%
Reference4530 Ω ±0.1%
Permissible input signalShort-term max. ±30 V
Gain±0.037%
Offset±0.0015%
Max. gain drift±0.004%/°C
Max. offset drift±0.00015%/°C
Nonlinearity<0.001%
Crosstalk between channels<-93 dB
G = 10.1 to 4500 Ω
G = 20.05 to 2250 Ω
50 Hz>80 dB
DC>95 dB
Range undershoot0x8001
Range overshoot0xFFFF
Open circuit0xFFFF
General fault0xFFFF
Open inputs0xFFFF
Electrical isolationChannel isolated from bus Channel not isolated from channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating
Starting temperatureYes, -40°C
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
OperationUp to 100%, condensing
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20cBM11 separately.
Pitch12.5 +0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20cAT4222”

Your email address will not be published. Required fields are marked *