Fast delivery within 72 Hours

B&R X20cAO4622

4 analog outputsEither current or voltage signal possible13-bit digital converter resolution

X20 analog output module, coated, 4 outputs,…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 analog outputsEither current or voltage signal possible13-bit digital converter resolution

X20 analog output module, coated, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution

Specification

I/O module4 analog outputs ±10 V or 0 to 20 mA / 4 to 20 mA
B&R ID code0xE212
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
Channel typeYes, using software
Bus0.01 W
Internal I/O1.8 W
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user’s manual)FTZÚ 09 ATEX 0083X
ULcULus E115267Industrial control equipment
HazLoccCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C)Humidity: B (up to 100%)Vibration: B (4 g)EMC: B (bridge and open deck)
LRENV1
KRYes
ABSYes
BVEC33BTemperature: 5 – 55°CVibration: 4 gEMC: Bridge and open deck
Output±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals
Max. output current10 mA at voltage >5 V15 mA at voltage <5 V
VoltageMax. 0.11%, from 10 MΩ → 1 kΩ, resistive
CurrentMax. 0.5%, from 1 Ω → 600 Ω, resistive
Conversion time300 µs for all outputs
Settling time on output change over entire range500 µs
Switch on/off behaviorInternal enable relay for startup
Gain±0.09%
Offset±0.05%
Output protectionShort-circuit proof
Short-circuit proofCurrent limiting ±40 mA
Output filterFirst-order low-pass filter / cutoff frequency 10 kHz
Nonlinearity<0.005%
Insulation voltage between channel and bus500 Veff
Electrical isolationChannel isolated from busChannel not isolated from channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
DeratingSee section “Derating”.
Starting temperatureYes, -40°C
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
OperationUp to 100%, condensing
NoteOrder 1x terminal block X20TB12 separately.Order 1x bus module X20cBM11 separately.
Pitch12.5+0.2 mm