The EQ3314 EtherCAT Box with analog inputs permits four thermocouples to be directly connected. The module’s circuit can operate thermocouple sensors using the 2-wire technique. Linearization over the full temperature range is realized with the aid of a
Specification
| Protocol | EtherCAT |
|---|---|
| Bus Interface | 2 x M8 socket, 4-pin, a-coded, shielded |
| Number Of Inputs | 4 |
| Connection Method | M12 socket, 2-wire connection for thermocouple |
| Conversion Time | 2.5 s up to 20 ms, see documentation, default: approx. 250 ms |
| Resolution | 0.1°C per digit |
| Sensor Types | types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement |
| Signal Type | thermocouple |
| Measuring Range | depending on sensor type; preset value is type K, -100…+1370°C |
| Measurement Error/Uncertainty | ±0.3% for type K (relative to full scale value; further types see documentation) |
| Nominal Voltage | 24 V DC (-15%/+20%) |
| Distributed Clocks | – |
| Input Filter | 5 variations, configurable |
| Current Consumption From Us | 120 mA |
| Power Supply Connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
| Electrical Isolation | 500 V |
| Special Features | stainless steel, Hygienic Design |
| Operating Temperature | -25…+60°C |
| Storage Temperature | -40…+85°C |
| Vibration/Shock Resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Emc Immunity/Emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. Rating/Installation Pos. | IP69K (according to EN 60529)/variable |
| Approvals/Markings | CE, UL |
| Dimensions (W X H X D) | 39 mm x 160 mm x 43 mm |
| Material | stainless steel |
| Installation | 2 fixing lugs for M5 |