Fast delivery within 72 Hours

Beckhoff EP3754-0002

The EP3754-0002 EtherCAT Box has four analog multifunctional inputs, which can be extensively parameterized on an individual basis: – voltage measurement: ±10 V, 0…10 V, 0…5 V – current measurement: ±…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

The EP3754-0002 EtherCAT Box has four analog multifunctional inputs, which can be extensively parameterized on an individual basis: – voltage measurement: ±10 V, 0…10 V, 0…5 V – current measurement: ±20 mA, 4…20 mA, 0…20 mA – resistance measurement: 0…5

Specification

ProtocolEtherCAT
Bus Interface2 x M8 socket, 4-pin, a-coded, shielded
Number Of Inputs4
Input ConnectionsM12 x 1, 5-pin, a-coded
Conversion Time~ 100 µs
Resolution16 bit (incl. sign)
Sensor Typesanalog sensors, thermocouple: type B, C, E, J, K, L, N, R, S, T, U, mV measurement, temperature: Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1.2/4 kΩ)
Signal Type-10/0…+10 V, -20mA/0/4…20 mA, RTD/Pt100/Pt1000, ±30/±60/±75 mV (thermocouple), parameterizable per channel
Common Mode Voltage Ucmmax. 15 V
Internal Resistance> 200 kΩ, typ. 85 Ω + diode voltage
Measurement Error/Uncertainty±0.3% (relative to full scale value)
Input Filter Limit Frequency5 kHz
Nominal Voltage24 V DC (-15%/+20%)
Distributed Clocksno
Input Filterconfigurable
Sensor Supplyfrom load supply voltage UP
Current Consumption From Us120 mA
Power Supply Connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical Isolation500 V
Special Featuresmulti-function, parameterizable
Operating Temperature-25…+60°C
Storage Temperature-40…+85°C
Vibration/Shock Resistanceconforms to EN 60068-2-6/EN 60068-2-27
Emc Immunity/Emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. Rating/Installation Pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/MarkingsCE, UL
Dimensions (W X H X D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3