Fast delivery within 72 Hours

B&R X67AO1223

4 analog outputs ±10 VIntegrated enable relay for initial phaseVery short cycle timesOptimal shield grounding on all channels

The module is equipped with 4…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 analog outputs ±10 VIntegrated enable relay for initial phaseVery short cycle timesOptimal shield grounding on all channels

The module is equipped with 4 inputs with 12-bit digital converter resolution. The output signal range is ±10 V.

Specification

I/O module

4 analog outputs ±10 V

B&R ID code

0x16F3

Status indicators

I/O function per channel, supply voltage, bus function

I/O power supply

M8, 4-pin

Outputs

4x M12, A-coded

Internal I/O

4 W

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 – Max. 60°C
TÜV 05 ATEX 7201X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

KC

Yes

Nominal voltage

24 VDC

Voltage range

18 to 30 VDC

Integrated protective function

Reverse polarity protection

Actuator power supply

Max. 12 W

Output

±10 V

Digital converter resolution

12-bit

Conversion time

400 µs for all outputs

Settling time on output change over entire range

Approx. 1 ms

Switch on/off behavior

Internal enable relay for startup and errors

Output protection

Protection against wiring with supply voltage, short-circuit proof

Output format

Example: INT 0x8001 – 0x7FFF / 1 LSB = 0x0010 = 4.882 mV

Load per channel

Max. ±10 mA, load ≥ 1 kΩ

Output filter

First-order low-pass filter / cutoff frequency 2.5 kHz

Max. gain drift

0.012%/°C

Max. offset drift

0.015%/°C

Error caused by load change

Max. 0.01%, from 10 MΩ → 1 kΩ, resistive

Nonlinearity

<0.15%

Insulation voltage between channel and bus

500 Veff

Output response when the power supply is switched on/off

An enable relay is switched on at a defined value ≠ 0, default setting = 10 kΩ to GND

Current limiting

±40 mA

To actuator or I/O power supply

Yes

To GND

Yes

Gain

0.15%

Offset

0.05%

Voltage

I/O power supply minus voltage drop for short-circuit protection

Voltage drop for short-circuit protection at 500 mA

Max. 2 VDC

Summation current

Max. 0.5 A

Short-circuit proof

Yes

Electrical isolation

Channel isolated from bus

Channel not isolated from channel

Any

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP67

Operation

-25 to 60°C

Derating

Storage

-40 to 85°C

Transport

-40 to 85°C

Width

53 mm

Height

85 mm

Depth

42 mm

Weight

190 g

M8

Max. 0.4 Nm

M12

Max. 0.6 Nm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X67AO1223”

Your email address will not be published. Required fields are marked *