Fast delivery within 72 Hours
B&R X67AO1223
4 analog outputs ±10 VIntegrated enable relay for initial phaseVery short cycle timesOptimal shield grounding on all channels
The module is equipped with 4…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
4 analog outputs ±10 VIntegrated enable relay for initial phaseVery short cycle timesOptimal shield grounding on all channels
The module is equipped with 4 inputs with 12-bit digital converter resolution. The output signal range is ±10 V.
Specification
| I/O module |
4 analog outputs ±10 V |
|---|---|
| B&R ID code |
0x16F3 |
| Status indicators |
I/O function per channel, supply voltage, bus function |
| I/O power supply |
M8, 4-pin |
| X2X Link |
M12, B-coded |
| Outputs |
4x M12, A-coded |
| Internal I/O |
4 W |
| X2X Link power supply |
0.75 W |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| KC |
Yes |
| Nominal voltage |
24 VDC |
| Voltage range |
18 to 30 VDC |
| Integrated protective function |
Reverse polarity protection |
| Actuator power supply |
Max. 12 W |
| Output |
±10 V |
| Digital converter resolution |
12-bit |
| Conversion time |
400 µs for all outputs |
| Settling time on output change over entire range |
Approx. 1 ms |
| Switch on/off behavior |
Internal enable relay for startup and errors |
| Output protection |
Protection against wiring with supply voltage, short-circuit proof |
| Output format |
Example: INT 0x8001 – 0x7FFF / 1 LSB = 0x0010 = 4.882 mV |
| Load per channel |
Max. ±10 mA, load ≥ 1 kΩ |
| Output filter |
First-order low-pass filter / cutoff frequency 2.5 kHz |
| Max. gain drift |
0.012%/°C |
| Max. offset drift |
0.015%/°C |
| Error caused by load change |
Max. 0.01%, from 10 MΩ → 1 kΩ, resistive |
| Nonlinearity |
<0.15% |
| Insulation voltage between channel and bus |
500 Veff |
| Output response when the power supply is switched on/off |
An enable relay is switched on at a defined value ≠0, default setting = 10 kΩ to GND |
| Current limiting |
±40 mA |
| To actuator or I/O power supply |
Yes |
| To GND |
Yes |
| Gain |
0.15% |
| Offset |
0.05% |
| Voltage |
I/O power supply minus voltage drop for short-circuit protection |
| Voltage drop for short-circuit protection at 500 mA |
Max. 2 VDC |
| Summation current |
Max. 0.5 A |
| Short-circuit proof |
Yes |
| Electrical isolation |
Channel isolated from bus Channel not isolated from channel |
| Any |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP67 |
| Operation |
-25 to 60°C |
| Derating |
– |
| Storage |
-40 to 85°C |
| Transport |
-40 to 85°C |
| Width |
53 mm |
| Height |
85 mm |
| Depth |
42 mm |
| Weight |
190 g |
| M8 |
Max. 0.4 Nm |
| M12 |
Max. 0.6 Nm |

Reviews