Fast delivery within 72 Hours
B&R X20cDO4332-1
4 digital outputs with 2 ASource circuit3-wire connections24 VDC and GND for actuator power supplyIntegrated output protectionOSP modePWM mode
The module i…
Shipping & Delivery
- 
Courier delivery
 
Our courier will deliver to the specified address
2-3 Days
From $20
- 
DHL Courier delivery
 
DHL courier will deliver to the specified address
2-3 Days
From $40
- 
Warranty 1 year
 
- 
Free 30-Day returns
 
Description
4 digital outputs with 2 ASource circuit3-wire connections24 VDC and GND for actuator power supplyIntegrated output protectionOSP modePWM mode
The module is equipped with 4 outputs with 3-wire connections as well as 24 VDC and GND for the actuator power supply. The outputs are designed for a source circuit. The nominal output current is 2 A.
Specification
| I/O module | 
 4 digital outputs 24 VDC for 3-wire connections  | 
|---|---|
| B&R ID code | 
 0x2A01  | 
| Status indicators | 
 I/O function per channel, operating state, module status  | 
| Module run/error | 
 Yes, using LED status indicator and software  | 
| Outputs | 
 Yes, using LED status indicator and software (output error status)  | 
| Bus | 
 0.1 W (Rev. <D0: 0.16 W)  | 
| Internal I/O | 
 0.49 W  | 
| Additional power dissipation caused by actuators (resistive) [W] | 
 +1 (Rev. <D0: +1.6)  | 
| CE | 
 Yes  | 
| UKCA | 
 Yes  | 
| CRA (Cyber Resilience Act) | 
 In preparation  | 
| DNV | 
 Temperature: B (0 to 55°C)  | 
| LR | 
 ENV1  | 
| KR | 
 Yes  | 
| ABS | 
 Yes  | 
| BV | 
 EC33B  | 
| Variant | 
 Current-sourcing FET  | 
| Nominal voltage | 
 24 VDC  | 
| Switching voltage | 
 24 VDC -15% / +20%  | 
| Nominal output current | 
 2 A  | 
| Total nominal current | 
 8 A  | 
| Connection type | 
 3-wire connections  | 
| Output circuit | 
 Source  | 
| Output protection | 
 Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current")  | 
| Actuator power supply | 
 Max. 12 W  | 
| Diagnostic status | 
 Output monitoring with 10 ms delay  | 
| Leakage current when the output is switched off | 
 5 µA  | 
| RDS(on) | 
 60 mΩ (Rev. <D0: 100 mΩ)  | 
| Peak short-circuit current | 
 <4 A  | 
| Switch-on in the event of overload shutdown or short-circuit shutdown | 
 Approx. 10 ms (depends on the module temperature)  | 
| 0 → 1 | 
 <300 µs  | 
| 1 → 0 | 
 <300 µs  | 
| Resistive load | 
 Max. 500 Hz  | 
| Braking voltage when switching off inductive loads | 
 0.6 V  | 
| Insulation voltage between channel and bus | 
 500 Veff  | 
| Additional functions | 
 Outputs can be connected in parallel to increase the output current.  | 
| Quantity | 
 4  | 
| Nominal current | 
 2 A  | 
| PWM frequency | 
 15.25 to 1000 Hz  | 
| Configurable dither | 
 0 to 250 Hz, 1 to 25% of the period duration  | 
| Period duration resolution | 
 1000 to 65535 µs in 1 µs steps  | 
| Voltage | 
 Module power supply minus voltage drop for short-circuit protection  | 
| Voltage drop for short-circuit protection at 500 mA | 
 Max. 2 V  | 
| Short-circuit proof | 
 Yes  | 
| Electrical isolation | 
 Channel isolated from bus  | 
| Horizontal | 
 Yes  | 
| Vertical | 
 Yes  | 
| 0 to 2000 m | 
 No limitation  | 
| >2000 m | 
 Reduction of ambient temperature by 0.5°C per 100 m  | 
| Degree of protection per EN 60529 | 
 IP20  | 
| Horizontal mounting orientation | 
 -25 to 60°C  | 
| Vertical mounting orientation | 
 -25 to 50°C  | 
| Derating | 
 See section "Derating".  | 
| Storage | 
 5 to 95%, non-condensing  | 
| Transport | 
 5 to 95%, non-condensing  | 
| Operation | 
 Up to 100%, condensing  | 
| Note | 
 Order 1x terminal block X20TB12 separately.  | 
| Pitch | 
 12.5+0.2 mm  | 
	
	
				
				
		
		
		
		
		
		
		
Reviews
Clear filtersThere are no reviews yet.