Amplifier Unit PNP. AP-40P. Series: Separate Amplifier Type Pressure Sensor. Series code: AP-40 series

Specification

Model Name

Amplifier Unit PNP

Model Code

AP-40P

Series Title

Separate Amplifier Type Pressure Sensor

Series Code

AP-40 series

Data Sheet URL

https://www.keyence.com/download/download/confirmation/?dlSeriesId=WS_SR_ap_40&dlModelId=PM_07540P&dlSiteId=1&dlLanguageId=en-US&dlLangType=en-US

CAD URL

https://www.keyence.com/products/process/pressure/ap-40/downloads/?mode=cd&modelId=PM_07540P

Manuals URL

https://www.keyence.com/products/process/pressure/ap-40/downloads/?mode=ma&modelId=PM_07540P

Model

AP-40P

Type

Main unit, PNP

Applicable sensor head

AP-41, AP-43, AP-44

Rated pressure

-15 to +110 % of F.S.

Display

3 1/2-digit, 2-color, 7-segment LED (Character height: 11 mm 0.43"), Display cycle: 5 times/sec.

Display resolution

AP-41: 0.1 kPa, 1 mmHg, 0.1 inchHg, 0.001 barAP-43: 0.001 MPa, 0.01 kgf/cm2, 0.2 Psi, 0.01 barAP-44: 0.2 kPa, 2 mmHg, 0.1 inchHg, 0.002 bar

Display temperature characteristic

±1.0 % of F.S.

Temperature fluctuation for analog output

±2.0 % of F.S.

Mounting

With supplied mounting bracket (2 types) or optional panel mounting bracket

Response time (Chattering prevention function)

2.5/5/100/500 ms

I/O - Control output

PNP open-collector: 100 mA max. (30 V max.), Residual voltage: 1 V max. 2-output (N.O./N.C. selectable)

I/O - Analog voltage output

1 to 5 V

Rating - Power voltage

12 to 24 VDC ±10 %, Ripple 10 % or less

Rating - Current consumption

105 mA (12 V), 55 mA (24 V) (including sensor head)

Environmental resistance - Ambient temperature

0 to +50 °C 32 to 122 °F (No freezing)

Environmental resistance - Relative humidity

35 to 85 % RH (No condensation)

Environmental resistance - Vibration resistance

10 to 55 Hz, Double amplitude 1.5 mm 0.06", 2 hours in each of the X, Y, and Z axis

Environmental resistance - Shock resistance

100 m/s2, 3 times in each of X, Y and Z axis

Material

Front housing: Polyamide, Rear housing: Polysulfone

Weight

80 g (including 2 m 6.6' cable) (28 g without cable)