Fast delivery within 72 Hours
B&R X67BCE321.L12
Fieldbus: PROFINET IOI/O configuration via the fieldbusConformance Class B (RT)1 ms minimum cycle timeIntegrated switch for wiring multiple slaves100 Mbit/s full-duplex modeUp to 1440 bytes of input d…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
Fieldbus: PROFINET IOI/O configuration via the fieldbusConformance Class B (RT)1 ms minimum cycle timeIntegrated switch for wiring multiple slaves100 Mbit/s full-duplex modeUp to 1440 bytes of input data and up to 1440 bytes of output data are possibleIntegrated websitePROFINET diagnostics and module diagnostics during runtime from within the master environmentModule and switch diagnostics during runtime using the website or SNMP16 digital channels, configurable as inputs or outputsIntegrated connection for additional 253 modules via X2X Link
PROFINET (Process Field Network) is an Industrial Ethernet protocol. It uses TCP/IP and is real-time capable. X67 modules or other modules that are based on X2X Link can be connected to the bus controller. Modular system configurations are optimally supported by PROFINET. Using the device description file (GSDML format), it is very easy to handle project configuration in the respective engineering tool from the manufacturer of the master device.
Specification
| Bus controller |
0xC5E8 |
|---|---|
| Inputs/Outputs |
8x M12, A-coded |
| Insulation voltage between channel and bus |
500 Veff |
| Nominal voltage |
24 VDC |
| Internal I/O module |
0xD9CB |
| Sensor/Actuator power supply |
Max. 12 W |
| Status indicators |
I/O function per channel, supply voltage, bus function |
| Outputs |
Yes, using LED status indicator and software |
| I/O power supply |
M8, 4-pin |
| Fieldbus |
1 ms |
| X2X Link |
250 μs |
| Power output |
15 W X2X Link power supply for I/O modules |
| Internal I/O |
2.5 W |
| X2X Link power supply |
24.3 W at maximum power output for connected I/O modules |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| Conformance class |
B |
| Performance class |
RT |
| Variant |
Current-sourcing FET |
| Line length |
Max. 100 m between 2 stations (segment length) |
| Transfer rate |
100 Mbit/s |
| Physical layer |
100BASE-TX |
| Half-duplex |
Yes |
| Full-duplex |
Yes |
| Autonegotiation |
Yes |
| Auto-MDI/MDIX |
Yes |
| Synchronization between bus systems possible |
Yes |
| Voltage range |
18 to 30 VDC |
| Integrated protective function |
Reverse polarity protection |
| Voltage |
I/O power supply minus voltage drop for short-circuit protection |
| Voltage drop for short-circuit protection at 0.5 A |
Max. 2 VDC |
| Summation current |
Max. 0.5 A |
| Short-circuit proof |
Yes |
| Input characteristics per EN 61131-2 |
Type 1 |
| Input voltage |
18 to 30 VDC |
| Input current at 24 VDC |
Typ. 4 mA |
| Input circuit |
Sink |
| Hardware |
≤10 μs (channels 1 to 4) / ≤70 µs (channels 5 to 16) |
| Software |
Default 0 ms, configurable between 0 and 25 ms in 0.2 ms intervals |
| Input resistance |
Typ. 6 kΩ |
| Additional functions |
50 kHz event counting, gate measurement |
| Low |
<5 VDC |
| High |
>15 VDC |
| Quantity |
1 |
| Signal form |
Square wave pulse |
| Evaluation |
Positive edge – Negative edge |
| Input frequency |
Max. 50 kHz |
| Counter 1 |
Input 1 |
| Counter 2 |
Input 3 |
| Counter frequency |
Max. 50 kHz |
| Counter size |
16-bit |
| Internal |
48 MHz, 3 MHz, 187.5 kHz |
| Length of pause between pulses |
≥100 µs |
| Pulse length |
≥20 µs |
| Supported inputs |
Input 2 |
| Switching voltage |
I/O power supply minus residual voltage |
| Nominal output current |
0.5 A |
| Total nominal current |
8 A |
| Output circuit |
Source |
| Output protection |
Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply |
| Diagnostic status |
Output monitoring with 10 ms delay |
| Leakage current when the output is switched off |
5 µA |
| Switching on after overload shutdown |
Approx. 10 ms (depends on the module temperature) |
| Residual voltage |
<0.3 V at 0.5 A nominal current |
| Peak short-circuit current |
<12 A |
| 0 → 1 |
<400 µs |
| 1 → 0 |
<400 µs |
| Resistive load |
Max. 100 Hz |
| Inductive load |
See section "Switching inductive loads". |
| Braking voltage when switching off inductive loads |
50 VDC |
| Electrical isolation |
Bus isolated from PROFINET and channel |
| Any |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP67 |
| Operation |
-25 to 60°C |
| Derating |
– |
| Storage |
-40 to 85°C |
| Transport |
-40 to 85°C |
| Width |
53 mm |
| Height |
155 mm |
| Depth |
42 mm |
| Weight |
350 g |
| M8 |
Max. 0.4 Nm |
| M12 |
Max. 0.6 Nm |

Reviews
Clear filtersThere are no reviews yet.