Fast delivery within 72 Hours
B&R X67BC8780.L12
POWERLINK8 CAN interfacesM12 connectionsIntegrated hub for efficient cabling
This bus controller makes it possible to connect 8 CAN interfaces to the POWER…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
POWERLINK8 CAN interfacesM12 connectionsIntegrated hub for efficient cabling
This bus controller makes it possible to connect 8 CAN interfaces to the POWERLINK network. The CAN interfaces are operated via an integrated hub, which increases the total cable length defined by classical CAN bus topology.POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The Ethernet POWERLINK Standardization Group (EPSG) ensures openness and continuous development: www.ethernet-powerlink.org.
Specification
| Bus controller |
0xED84 |
|---|---|
| Inputs/Outputs |
8x M12, A-coded |
| Insulation voltage between channel and bus |
500 Veff |
| Nominal voltage |
24 VDC |
| Status indicators |
TX/RX per CAN interface, supply voltage, bus function |
| Outputs |
Yes, using LED status indicator and software |
| Power supply |
Yes, using LED status indicator and software |
| Dynamic node allocation (DNA) |
Yes |
| Fieldbus |
M12, D-coded |
| I/O power supply |
M8, 4-pin |
| Internal I/O |
2.5 W |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| Type |
CAN |
| Variant |
8x M12 interface (hub) |
| Line length |
Max. 100 m between 2 stations (segment length) |
| Transfer rate |
Bus length ≤25 m: Max. 500 kbps |
| Physical layer |
100BASE-TX |
| Half-duplex |
Yes |
| Full-duplex |
No |
| Autonegotiation |
Yes |
| Auto-MDI/MDIX |
Yes |
| Hub propagation delay |
250 ns |
| Cycle time |
200 µs |
| Max. distance |
1000 m |
| Terminating resistor |
Integrated in module |
| Voltage |
9 to 32 V |
| Voltage drop for short-circuit protection at 0.5 A |
Max. 2 VDC |
| Summation current |
Max. 1.6 A (200 mA per channel) |
| Short-circuit proof |
Yes |
| Voltage range |
9 to 32 VDC |
| Reverse polarity protection |
Yes |
| Electrical isolation |
POWERLINK isolated from channel |
| Any |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP67 |
| Operation |
-25 to 60°C |
| Derating |
– |
| Storage |
-40 to 85°C |
| Transport |
-40 to 85°C |
| Width |
53 mm |
| Height |
155 mm |
| Depth |
42 mm |
| M8 |
Max. 0.4 Nm |
| M12 |
Max. 0.6 Nm |