B&R X67BC7321-1

Fieldbus: CAN bus8 digital channels, configurable as inputs or outputsIntegrated I/O access in B&R Automation StudioAutomatic firmware update via the fieldbusX67 connection possibility for all B&R CPU…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Fieldbus: CAN bus8 digital channels, configurable as inputs or outputsIntegrated I/O access in B&R Automation StudioAutomatic firmware update via the fieldbusX67 connection possibility for all B&R CPUs

The bus controller makes it possible to connect X2X Link I/O nodes to CAN I/O. CAN I/O is a transfer protocol based on standard CAN bus that is fully integrated in the B&R system.Up to 43 logic I/O modules can be connected to the bus controller. Up to 16 of them can be analog modules.With multifunction modules, the bus controller supports only the default function model in the event of automatic configuration by the bus controller (see the respective module description).

Specification

Bus controller

0x18CB

Inputs/Outputs

8x M8, 3-pin

Insulation voltage between channel and bus

500 Veff

Nominal voltage

24 VDC

Internal I/O module

0x1311

Sensor/Actuator power supply

Max. 12 W

Status indicators

I/O function per channel, supply voltage, bus function

Outputs

Yes, using LED status indicator and software

I/O power supply

M8, 4-pin

Fieldbus

CAN I/O

Power output

3 W X2X Link power supply for I/O modules

Internal I/O

2 W

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA IIA T5 Gc
IP67, Ta = 0 – Max. 60°C
TÜV 05 ATEX 7201X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

KC

Yes

Variant

Current-sourcing FET

Max. distance

1000 m

Transfer rate

Max. 1 Mbit/s

Default transfer rate

Automatic transfer rate detection

Synchronization between bus systems possible

No

Terminating resistor

Can be optionally screwed onto the Y-connector

Voltage range

18 to 30 VDC

Integrated protective function

Reverse polarity protection

Voltage

I/O power supply minus voltage drop for short-circuit protection

Voltage drop for short-circuit protection at 0.5 A

Max. 2 VDC

Summation current

Max. 0.5 A

Short-circuit proof

Yes

Input characteristics per EN 61131-2

Type 1

Input voltage

18 to 30 VDC

Input current at 24 VDC

Typ. 4 mA

Input circuit

Sink

Hardware

≤10 μs (channels 1 to 4) / ≤70 µs (channels 5 to 8)

Software

Default 0 ms, configurable between 0 and 25 ms in 0.2 ms intervals

Input resistance

Typ. 6 kΩ

Additional functions

50 kHz event counting, gate measurement

Low

<5 VDC

High

>15 VDC

Quantity

1

Signal form

Square wave pulse

Evaluation

Positive edge – Negative edge

Input frequency

Max. 50 kHz

Counter 1

Input 1

Counter 2

Input 3

Counter frequency

Max. 50 kHz

Counter size

16-bit

Internal

48 MHz, 3 MHz, 187.5 kHz

Length of pause between pulses

≥100 µs

Pulse length

≥20 µs

Supported inputs

Input 2 or input 4

Switching voltage

I/O power supply minus residual voltage

Nominal output current

0.5 A

Total nominal current

4 A

Output circuit

Source

Output protection

Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply

Diagnostic status

Output monitoring with 10 ms delay

Leakage current when the output is switched off

5 µA

Switching on after overload shutdown

Approx. 10 ms (depends on the module temperature)

Residual voltage

<0.3 V at 0.5 A nominal current

Peak short-circuit current

<12 A

0 → 1

<400 µs

1 → 0

<400 µs

Resistive load

Max. 100 Hz

Inductive load

See section "Switching inductive loads".

Braking voltage when switching off inductive loads

50 VDC

Electrical isolation

Channel isolated from CAN I/O and bus
CAN I/O not isolated from bus and channel not isolated from channel

Any

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP67

Operation

-25 to 60°C

Derating

Storage

-40 to 85°C

Transport

-40 to 85°C

Width

53 mm

Height

85 mm

Depth

42 mm

Weight

195 g

M8

Max. 0.4 Nm

M12

Max. 0.6 Nm