Specification
| I/O module |
8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B2 digital outputs, 24 VDC, 50 mA, OSSD <500 µs, SafeLOGIC-X technology |
|---|---|
| B&R ID code |
0x2F20 |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Outputs |
Yes, using LED status indicator and software |
| Inputs |
Yes, using LED status indicator and software |
| Scope |
Module |
| Function |
Programmable |
| Standalone mode |
Yes |
| Max. I/O cycle time |
800 µs |
| Bus |
0.4 W |
| Internal I/O |
2.5 W |
| Safe digital HS-LS outputs |
0.84 |
| Safe digital HS-HS outputs |
0.175 |
| Pulse outputs |
0.8 |
| Channel - Bus |
Yes |
| Channel - Channel |
No |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| Functional safety |
EN 50156-1:2004 |
| ATEX |
In preparation |
| UL |
In preparation |
| Note |
Order 2x safety-keyed terminal block separately. |
| Quantity |
4 |
| Variant |
Push-Pull |
| Nominal voltage |
24 VDC |
| Input characteristics per EN 61131-2 |
Type 1 |
| Hardware |
≤150 µs |
| Software |
Configurable between 0 and 500 ms |
| Input circuit |
Sink |
| Input voltage |
24 VDC -15% / +20% |
| Input current at 24 VDC |
Min. 2 mA to max. 3.28 mA |
| Input resistance |
Min. 7.33 kΩ |
| Error detection time |
1 s |
| Insulation voltage between channel and bus |
500 Veff |
| Low |
<5 VDC |
| High |
>15 VDC |
| Line length between signal source (pulse output or external signal) and input |
Max. 60 m with unshielded line |
| Nominal output current |
50 mA |
| Total nominal current |
200 mA |
| Output protection |
Shutdown of individual channels in the event of overload or short circuit |
| Braking voltage when switching off inductive loads |
Max. 45 VDC |
| Error detection |
1 s |
| Peak short-circuit current |
0.5 A for 120 µs |
| Leakage current when the output is switched off |
0.1 mA |
| RDS(on) |
80 Ω |
| Switching voltage |
I/O power supply minus voltage drop due to RDS(on) |
| Max. switching frequency |
See section "Inrush current behavior for output channels". |
| Test pulse length |
Max. 500 µs |
| Max. capacitive load |
100 nF |
| IOUT |
<100 µA |
| IGND |
<50 mA |
| Short-circuit current |
15 mAeff |
| Horizontal |
Yes |
| Vertical |
Yes |
| Installation elevation above sea level |
0 to 2000 m, no limitation |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
0 to 60°C |
| Vertical mounting orientation |
0 to 50°C |
| Derating |
See section "Derating". |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Pitch |
25+0.2 mm |