B&R X20SLX842
openSAFETY manager for up to 10 SafeNODEsFlexibly programmable using Automation Studio / SafeDESIGNERInnovative management of safe machine options (SafeOPTION)Parameter and configuration management8 s…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
openSAFETY manager for up to 10 SafeNODEsFlexibly programmable using Automation Studio / SafeDESIGNERInnovative management of safe machine options (SafeOPTION)Parameter and configuration management8 safe digital inputs, sink circuit4 pulse outputsSoftware input filter configurable for each channel4 safe digital outputs, output type A with 3 A, source circuit2 safe digital outputs, output type B with 50 mA, source circuitIntegrated output protection
The module is equipped with SafeLOGIC functionality that allows it to safely execute applications designed in SafeDESIGNER. The module can be used in safety-related applications up to PL e or SIL 3.In addition, the module coordinates the safety-related communication of all modules involved in the application. In this context, the module also monitors the configuration of these modules and carries out autonomous parameter downloads to the modules whenever necessary. This guarantees a consistent and correct module configuration in the network from a safety standpoint in all scenarios involving module replacement and service. These services are performed in conjunction with Automation Runtime on the standard CPU.In addition, SafeLOGIC-X products have the same I/O properties as the associated SafeIO products (X20SC0xxx).
Specification
| I/O module |
8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B2 digital outputs, 24 VDC, 50 mA, OSSD <500 µs, SafeLOGIC-X technology |
|---|---|
| B&R ID code |
0xE7EB |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Outputs |
Yes, using LED status indicator and software |
| Inputs |
Yes, using LED status indicator and software |
| Scope |
Module |
| Function |
Programmable |
| Standalone mode |
Yes |
| Max. I/O cycle time |
1 ms |
| Bus |
0.4 W |
| Internal I/O |
2.5 W |
| Safe digital HS-LS outputs |
0.84 |
| Safe digital HS-HS outputs |
0.175 |
| Pulse outputs |
0.8 |
| Channel - Bus |
Yes |
| Channel - Channel |
No |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| Functional safety |
EN 50156-1:2004 |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| Note |
Order 2x safety-keyed terminal block separately. |
| FB instances |
256 |
| Marker memory |
5120 bytes (0x1400) |
| Stack memory |
4096 bytes |
| Memory for safe input data |
128 bytes, 68 bytes of which are usable for modules |
| Memory for safe output data |
64 bytes |
| Memory for standard input data |
64 bytes |
| Memory for standard output data |
64 bytes |
| Marker count |
256 |
| Max. number of function block types |
64 |
| Max. number of force variables |
8 |
| Max. number of variable with variable status |
128 |
| Nominal voltage |
24 VDC |
| Voltage range |
24 VDC -15% / +20% |
| Integrated protective function |
Reverse polarity protection |
| Quantity |
4 |
| Variant |
Push-Pull |
| Input characteristics per EN 61131-2 |
Type 1 |
| Hardware |
≤150 µs |
| Software |
Configurable between 0 and 500 ms |
| Input circuit |
Sink |
| Input voltage |
24 VDC -15% / +20% |
| Input current at 24 VDC |
Min. 2 mA to max. 3.28 mA |
| Input resistance |
Min. 7.33 kΩ |
| Error detection time |
1 s |
| Insulation voltage between channel and bus |
500 Veff |
| Low |
<5 VDC |
| High |
>15 VDC |
| Line length between signal source (pulse output or external signal) and input |
Max. 60 m with unshielded line |
| Nominal output current |
50 mA |
| Total nominal current |
200 mA |
| Output protection |
Shutdown of individual channels in the event of overload or short circuit |
| Braking voltage when switching off inductive loads |
Max. 45 VDC |
| Error detection |
1 s |
| Peak short-circuit current |
0.5 A for 120 µs |
| Leakage current when the output is switched off |
0.1 mA |
| RDS(on) |
80 Ω |
| Switching voltage |
I/O power supply minus voltage drop due to RDS(on) |
| Max. switching frequency |
See section "Inrush current behavior for output channels". |
| Test pulse length |
Max. 500 µs |
| Max. capacitive load |
100 nF |
| IOUT |
<100 µA |
| IGND |
<50 mA |
| Short-circuit current |
15 mAeff |
| Horizontal |
Yes |
| Vertical |
Yes |
| Installation elevation above sea level |
0 to 2000 m, no limitation |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
0 to 60°C |
| Vertical mounting orientation |
0 to 50°C |
| Derating |
See section "Derating". |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Pitch |
25+0.2 mm |

Reviews
Clear filtersThere are no reviews yet.