Fast delivery within 72 Hours
B&R X20SL8101
openSAFETY manager for up to 280 SafeNODEsFlexibly programmable using Automation Studio / SafeDESIGNERInnovative management of safe machine options (SafeOPTION)Parameter and configuration management…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
openSAFETY manager for up to 280 SafeNODEsFlexibly programmable using Automation Studio / SafeDESIGNERInnovative management of safe machine options (SafeOPTION)Parameter and configuration management
The module is equipped with SafeLOGIC functionality that allows it to safely execute applications designed in SafeDESIGNER. The module can be used in safety-related applications up to PL e or SIL 3.In addition, the module coordinates the safety-related communication of all modules involved in the application. In this context, the module also monitors the configuration of these modules and carries out autonomous parameter downloads to the modules whenever necessary. This guarantees a consistent and correct module configuration in the network from a safety standpoint in all scenarios involving module replacement and service. These services are performed by the SafeLOGIC controller.
Specification
| Interfaces |
POWERLINK |
|---|---|
| System module |
CPU |
| B&R ID code |
0xE649 |
| Cooling |
Fanless |
| Status indicators |
CPU function, POWERLINK, SafeKEY |
| CPU function |
Yes, using LED status indicator |
| POWERLINK |
Yes, using LED status indicator |
| SafeKEY |
Yes, using LED status indicator |
| Dynamic node allocation (DNA) |
Yes |
| Scope |
Network segment |
| Function |
Programmable |
| Standalone mode |
Yes |
| Power consumption |
5.3 W |
| Power consumption for X2X Link power supply |
1.42 W |
| Internal I/O |
0.6 W |
| Additional power dissipation caused by actuators (resistive) [W] |
– |
| Fieldbus - X2X Link |
Yes |
| Fieldbus - I/O |
Yes |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| Functional safety |
EN 50156-1:2004 |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL |
cULus E115267Industrial control equipment |
| HazLoc |
cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV |
Temperature: A (0 to 45°C)Humidity: B (up to 100%)Vibration: A (0.7 g)EMC: B (bridge and open deck) |
| CCS |
Yes |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| BV |
EC21BTemperature: 5 – 45°CVibration: 0.7 gEMC: Bridge and open deck |
| Note |
Order SafeKEY and SafeLOGIC range of functions using the X20MK configurator.X20 end cover plate (right) included in delivery12-pin X20 terminal block, safety-keyed, included in deliverySafeKEY cover included in delivery |
| FB instances |
4096 |
| Marker memory |
262,144 bytes |
| Stack memory |
32,768 bytes |
| Memory for safe input data |
6144 bytes |
| Memory for safe output data |
2048 bytes |
| Memory for standard input data |
1024 bytes |
| Memory for standard output data |
1024 bytes |
| Marker count |
16,382 |
| Max. number of function block types |
512 |
| Max. number of force variables |
64 |
| Max. number of variable with variable status |
1023 |
| Input voltage |
24 VDC -15% / +20% |
| Input current |
Max. 0.9 A |
| Fuse |
Required line fuse: Max. 10 A, slow-blow |
| Reverse polarity protection |
Yes |
| Nominal output power |
7 W |
| Parallel connection |
Yes |
| Redundant operation |
Yes |
| Overload characteristics |
Short-circuit proof, temporary overload |
| Nominal output voltage |
24 VDC |
| Behavior on short circuit |
Required line fuse |
| Permissible contact load |
10 A |
| Fieldbus |
200 µs |
| Variant |
2x shielded RJ45 port (hub) |
| Line length |
Max. 100 m between 2 nodes (segment length) |
| Transfer rate |
100 Mbit/s |
| Physical layer |
100BASE-TX |
| Half-duplex |
Yes |
| Full-duplex |
No |
| Autonegotiation |
Yes |
| Auto-MDI/MDIX |
Yes |
| X2X Link |
200 µs |
| Synchronization between bus systems possible |
Yes |
| Horizontal |
Yes |
| Vertical |
Yes |
| Installation elevation above sea level |
0 to 2000 m, no limitation |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
0 to 60°C |
| Vertical mounting orientation |
0 to 45°C |
| Derating |
See section "Derating". |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Width |
62.5+0.2 mm |
| Height |
99 mm |
| Depth |
75 mm |
| Weight |
190 g |

Reviews