B&R X20SD1207
1 safe digital counter input with up to 7 kHz counter frequencyFor encoder inputs A-A, A-B, A-A/-B-B/Sink circuitInput filter configurable
This module is e…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
1 safe digital counter input with up to 7 kHz counter frequencyFor encoder inputs A-A, A-B, A-A/-B-B/Sink circuitInput filter configurable
This module is equipped with 1 safe digital input for determining the velocity. Velocity information can be acquired from AB signals up to a maximum frequency of 7 kHz.The safe counter module is suitable for safely acquiring velocities for safety-related applications up to PL e or SIL 3.This module is designed for X20 12-pin terminal blocks.
Specification
| I/O module |
1 safe type A digital counter channel, 7 kHz, 24 VDC |
|---|---|
| B&R ID code |
0xCAC1 |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Inputs |
Yes, using LED status indicator and software |
| Scope |
Module |
| Function |
Module functionality |
| Standalone mode |
No |
| Max. I/O cycle time |
2 ms |
| Bus |
0.25 W |
| Internal I/O |
0.75 W |
| Additional power dissipation caused by actuators (resistive) [W] |
0.064 |
| Channel - Bus |
Yes |
| Channel - Channel |
No |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| Functional safety |
EN 50156-1:2004 |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL |
cULus E115267Industrial control equipment |
| HazLoc |
cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV |
Temperature: A (0 to 45°C)Humidity: B (up to 100%)Vibration: A (0.7 g)EMC: B (bridge and open deck) |
| CCS |
Yes |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| BV |
EC21BTemperature: 5 – 45°CVibration: 0.7 gEMC: Bridge and open deck |
| KC |
Yes |
| Note |
Order 1x safety-keyed terminal block separately.Order 1x safety-keyed bus module separately. |
| Output voltage |
I/O power supply minus voltage drop due to RDS(on) |
| Nominal output current |
80 mA |
| RDS(on) |
10 Ω |
| Short-circuit proof |
Thermal limit determined by PTC |
| Nominal voltage |
24 VDC |
| Voltage range |
24 VDC -15% / +20% |
| Integrated protective function |
Reverse polarity protection |
| Quantity |
1 |
| Variant |
Type A |
| Input characteristics per EN 61131-2 |
Type 1 |
| Hardware |
<10 µs |
| Software |
Configurable between 0 and 100 s |
| Input frequency |
Max. 7 kHz |
| Input circuit |
Sink |
| Input voltage |
24 VDC -15% / +20% |
| Input current at 24 VDC |
Min. 2 mA to max. 2.48 mA |
| Input resistance |
9.68 kΩ |
| Insulation voltage between channel and bus |
500 Veff |
| Low |
<5 VDC |
| High |
>15 VDC |
| Line length |
Max. 30 m shielded |
| Horizontal |
Yes |
| Vertical |
Yes |
| Installation elevation above sea level |
0 to 2000 m, no limitation |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
0 to 60°C |
| Vertical mounting orientation |
0 to 50°C |
| Derating |
See section "Derating". |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Pitch |
25+0.2 mm |