Fast delivery within 72 Hours
B&R X20SD1207
1 safe digital counter input with up to 7 kHz counter frequencyFor encoder inputs A-A, A-B, A-A/-B-B/Sink circuitInput filter configurable
This module is e…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
1 safe digital counter input with up to 7 kHz counter frequencyFor encoder inputs A-A, A-B, A-A/-B-B/Sink circuitInput filter configurable
This module is equipped with 1 safe digital input for determining the velocity. Velocity information can be acquired from AB signals up to a maximum frequency of 7 kHz.The safe counter module is suitable for safely acquiring velocities for safety-related applications up to PL e or SIL 3.This module is designed for X20 12-pin terminal blocks.
Specification
| I/O module | 1 safe type A digital counter channel, 7 kHz, 24 VDC |
|---|---|
| B&R ID code | 0xCAC1 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Inputs | Yes, using LED status indicator and software |
| Scope | Module |
| Function | Module functionality |
| Standalone mode | No |
| Max. I/O cycle time | 2 ms |
| Bus | 0.25 W |
| Internal I/O | 0.75 W |
| Additional power dissipation caused by actuators (resistive) [W] | 0.064 |
| Channel - Bus | Yes |
| Channel - Channel | No |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| Functional safety | EN 50156-1:2004 |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user’s manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: A (0 to 45°C)Humidity: B (up to 100%)Vibration: A (0.7 g)EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC21BTemperature: 5 – 45°CVibration: 0.7 gEMC: Bridge and open deck |
| KC | Yes |
| Note | Order 1x safety-keyed terminal block separately.Order 1x safety-keyed bus module separately. |
| Output voltage | I/O power supply minus voltage drop due to RDS(on) |
| Nominal output current | 80 mA |
| RDS(on) | 10 Ω |
| Short-circuit proof | Thermal limit determined by PTC |
| Nominal voltage | 24 VDC |
| Voltage range | 24 VDC -15% / +20% |
| Integrated protective function | Reverse polarity protection |
| Quantity | 1 |
| Variant | Type A |
| Input characteristics per EN 61131-2 | Type 1 |
| Hardware | <10 µs |
| Software | Configurable between 0 and 100 s |
| Input frequency | Max. 7 kHz |
| Input circuit | Sink |
| Input voltage | 24 VDC -15% / +20% |
| Input current at 24 VDC | Min. 2 mA to max. 2.48 mA |
| Input resistance | 9.68 kΩ |
| Insulation voltage between channel and bus | 500 Veff |
| Low | <5 VDC |
| High | >15 VDC |
| Line length | Max. 30 m shielded |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | 0 to 60°C |
| Vertical mounting orientation | 0 to 50°C |
| Derating | See section “Derating”. |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Pitch | 25+0.2 mm |