Fast delivery within 72 Hours

B&R X20SA4430

2 safe analog input pairs for current measurement 0.5 to 25 mA24-bit digital converter resolutionChannels individually galvanically isolatedSensor power supplies galvanically isolatedInput filter conf…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

2 safe analog input pairs for current measurement 0.5 to 25 mA24-bit digital converter resolutionChannels individually galvanically isolatedSensor power supplies galvanically isolatedInput filter configurable

The module is equipped with 2 safe analog input pairs for current measurement. Each input pair has its own sensor power supply. The channels with their respective sensor supplies are electrically isolated from each other. It can be used to capture current signals in the range from 0.5 to 25 mA.The safe analog input module is suitable for safely acquiring current signals for safety-related applications up to PL e or SIL 3.This module is designed for X20 16-pin terminal blocks.

Specification

I/O module2x 2 safe type A analog inputs, 0.5 to 25 mA, channels individually galvanically isolated
B&R ID code0xB8B5
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time2 ms
Bus0.25 W
Internal I/O1.7 W
Additional power dissipation caused by actuators (resistive) [W]0.36
Channel - Bus500 VDC
Channel - ChannelYes
Channel pair - Channel pair500 VDC
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC21B Temperature: 5 – 45°C Vibration: 0.7 g EMC: Bridge and open deck
KCYes
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Nominal voltage29 VDC ±5%
Voltage range24 VDC -15% / +20%
Quantity2 safe input channel pairs
VariantType A
Input typeDifferential input
Digital converter resolution24-bit
Conversion timeSee chapter “I/O update time”.
Output formatSAFEINT
LoadUp to hardware revision D3: 230 to 420 Ω, hardware revision E0 or later: 185 to 245 Ω
Input protectionProtection against external supply voltages and overcurrent
Open-circuit detectionYes, using software
VoltageMax. 30.5 V
Conversion procedureSigma-delta
0.5 to <4 mA<0.735 µA/°C
4 to 25 mA<0.735 µA/°C
DC>70 dB
50 Hz>70 dB
Common-mode rangeBetween the inputs ±50 V
Nonlinearity<0.003%
Measurement range0.5 to 25 mA
HardwareFirst-order low-pass filter / cutoff frequency 500 Hz
SoftwareSinc3 filter
Resolution1 µA/LSB
Overload detectionYes, using software
Channel - Ground500 VDC
Cat. 30.184 mA
Cat. 40.49 mA
Filter timeConfigurable between 1 and 66.7 ms
Nominal output currentMax. 60 mA
Short-circuit proofYes, continuous
Sensor power supply - ChannelNo
Sensor power supply - Sensor power supplyYes
RDS(on)50 Ω
Behavior on short circuitVoltage cutoff
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Horizontal mounting orientation0 to 60°C
Vertical mounting orientation0 to 40°C
DeratingSee section “Derating”.
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
Pitch25+0.2 mm