Fast delivery within 72 Hours

B&R X20PD2113

Integrated exchangeable microfuseMonitoring of the fusePotential for routing as neededCan be used as feed module for the I/O supply

The potential distribut…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Integrated exchangeable microfuseMonitoring of the fusePotential for routing as neededCan be used as feed module for the I/O supply

The potential distributor module with feed can provide 6x 24 VDC and 6x ground connections from the internal I/O supply on the terminals. This module can also be used instead of a special feed module for the internal I/O supply. The internal 24 VDC supply is connected to the terminal connections through a replaceable microfuse for protection. The 24 VDC feed and the functionality of the fuse are monitored.

Specification

Potential distributor module with supply6x 24 VDC on the terminals, 6x ground on the terminals
B&R ID code0x267F
Status indicatorsOperating state, module status
Module run/errorYes, using LED status indicator and software
Fuse monitoringYes, using LED status indicator and software
Bus0.12 W
Internal I/O1.15 W
External I/O1.15 W
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck
KCYes
Nominal input voltage24 VDC -15% / +20% external, ground external
Input currentMax. 6 A
FuseIntegrated 6.3 A, slow-blow, can be replaced
Behavior on short circuitNo protection available Use an external fuse.
Reverse polarity protectionNo
Nominal output voltage24 VDC, ground
Permissible contact load6 A
On 24 VDC power supplyIntegrated fuse
On GND power supplyNo protection available
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM01 or X20BM11 separately.