Fast delivery within 72 Hours
B&R X20MM4456
4x outputs (H bridge) with PWM control and 24 to 48 VDC ±25% supply6 A nominal current (10 A max current)15 Hz to 50 kHz frequency, 16-bitPWM resolution, 15-bit, + sign, minimum 10 nsConfigurable dith…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
4x outputs (H bridge) with PWM control and 24 to 48 VDC ±25% supply6 A nominal current (10 A max current)15 Hz to 50 kHz frequency, 16-bitPWM resolution, 15-bit, + sign, minimum 10 nsConfigurable dither4x 4 inputs 24V, can be configured as ABRSink connection1-wire connections
The PMW motor bridge module is used to control 4 DC motors with a nominal voltage of 24 to 48 VDC ±25% at a nominal current up to 6 A.
Specification
| I/O module |
4-channel PWM motor bridge, 4 ABR incremental encoders |
|---|---|
| B&R ID code |
0xA177 |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Output |
Yes, using LED status indicator and software |
| I/O power supply |
Yes, using software |
| Bus |
0.01 W |
| Internal I/O |
2.4 W |
| 24 VDC |
2 W / channel |
| 48 VDC |
2.1 W / channel |
| 60 VDC |
2.2 W / channel |
| Additional power dissipation caused by actuators (resistive) [W] |
– |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cURus E225616 |
| HazLoc |
cCSAus 244665 |
| KC |
Yes |
| Quantity |
4 |
| Nominal voltage |
24 to 48 VDC ±25% |
| Input characteristics per EN 61131-2 |
Type 1 |
| Input voltage |
24 VDC (-15% / +20%) |
| Input current at 24 VDC |
Approx. 4 mA |
| Input circuit |
Sink |
| Hardware |
<5 µs |
| Software |
– |
| Connection type |
1-wire connections |
| Input resistance |
Typ. 6 kΩ |
| Additional functions |
4x ABR incremental encoder |
| Low |
<5 VDC |
| High |
>15 VDC |
| Insulation voltage between channel and bus |
500 Veff |
| Encoder inputs |
24 V, asymmetrical |
| Counter size |
16-bit |
| Input frequency |
Max. 50 kHz |
| Evaluation |
4x |
| Signal form |
Square wave pulse |
| Nominal current |
6 A |
| Maximum current |
10 A (2 s) |
| PWM frequency |
15 Hz to 50 kHz |
| Supply |
External |
| Fuse |
Required line fuse: Max. 32 A slow-blow (see "Overcurrent protection") |
| Output protection |
Thermal shutdown in the event of overcurrent or short circuit |
| Variant |
H bridge |
| Configurable dither |
Amplitude, frequency |
| Period duration resolution |
16-bit, min. 20 μs |
| Phase shift PWM1, 2, 3, 4 |
90° each |
| DC bus capacitance |
680 μF |
| PWM mode |
15 bits plus sign ≥10 ns |
| Current mode |
15 bits plus sign ≥10 ns |
| Electrical isolation |
Channel isolated from bus |
| Horizontal |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
0 to 50°C |
| Vertical mounting orientation |
Not permitted |
| Derating |
– |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Note |
Order 2x terminal block X20TB12 separately. |
| Pitch |
87.5+0.2 mm |

Reviews