B&R X20HB2886
Active hub expansion module2x 100 BASE-FX hub for redundant wiringHot-swap-capable
The X20BC8084 POWERLINK bus controller and the X20HB8884 module are equi…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
Active hub expansion module2x 100 BASE-FX hub for redundant wiringHot-swap-capable
The X20BC8084 POWERLINK bus controller and the X20HB8884 module are equipped with an integrated link selector function. An additional 1 or 2 slots are available, depending on the bus base used. The active X20HB2886 hub expansion module can be operated in these slots. Note that the hardware revision of the X20BC8084 and the X20HB8884 must be ≥E0.The active hub expansion module is equipped with one integrated 2x hub and allows redundant wiring. This means that the connection between the two 100 Base-FX interfaces remains intact if there is a failure in the bus controller or Compact Link Selector. The Ethernet connection is made using 62.5/125 μm or 50/125 µm fiber optic multimode cable with a duplex LC connection. The status of the module and network are indicated by LEDs.
Specification
| Hub |
2 Fast Ethernet interfaces for fiber optic cables for redundant wiring |
|---|---|
| Status indicators |
Module status, bus function |
| Module status |
Yes, using LED status indicator |
| Bus function |
Yes, using LED status indicator |
| Power consumption |
2.3 W (rev. <D0: 2.8 W) |
| Additional power dissipation caused by actuators (resistive) [W] |
– |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| KC |
Yes |
| Type |
Active hub expansion module |
| Variant |
2x female duplex LC |
| Transfer rate |
100 Mbit/s |
| Physical layer |
100BASE-FX |
| Half-duplex |
Max. 400 m between 2 stations (segment length) |
| Full-duplex |
No |
| Autonegotiation |
No |
| Auto-MDI/MDIX |
No |
| Hub propagation delay |
0.96 to 1 µs |
| Wave length |
Typ. 1300 nm Rx range: 1270 to 1380 nm Tx range: 1270 to 1380 nm |
| Cable fiber type |
Multimode fiber with 62.5/125 µm or 50/125 µm core diameter |
| Glass fiber 62.5/125 µm, NA = 0.275 |
11 dB |
| Glass fiber 50/125 µm, NA = 0.200 |
7.7 dB |
| POWERLINK |
Max. 2 km between 2 stations (segment length) |
| Electrical isolation |
Power supply isolated from Ethernet (IF1 and IF2) |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation (with ≥2 hubs) |
-25 to 50°C (Rev. <D0: 0 to 40°C) |
| Vertical mounting orientation (with ≥2 hubs) |
-25 to 35°C (Rev. <D0: 0 to 35°C) |
| Derating |
– |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Slot |
Hub expansion for X20BC8084 and X20HB8884 |