B&R X20ET8819

NetTime time stamp has a resolution of 20 nsRecording and analysis of CRC and frame errorsTriggers can also be activated using external digital signalsAnalysis of both half-duplex and full-duplex netw…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

NetTime time stamp has a resolution of 20 nsRecording and analysis of CRC and frame errorsTriggers can also be activated using external digital signalsAnalysis of both half-duplex and full-duplex networksAble to record two networks simultaneously

POWERLINK has proven itself in the field for years and rarely has problems during commissioning and production. Nonetheless, it is still possible for communication disturbances to occur due to damaged or poor quality cables. If an error occurs, localizing and correcting it is usually very easy thanks to the heterogeneous structure of this flat network type (all data is always visible throughout the network). What’s problematic are errors that occur sporadically. This is where tools such as Omnipeek or Wireshark come in.These tools (or more likely the standard PC technology being used) reach their limits, however, when dealing with machines that have short network cycles. Either not all frames can be recorded, or some telegrams are lost altogether. In these cases, what’s needed is a special hardware tool that can work very quickly, record and save every bit of traffic and then pass it on to a laptop.This module provides different operating modes. For example, it can work passively on the network, in which case the real-time behavior remains unchanged. The device listens in and selectively takes in data when certain defined trigger conditions are met. It can read all of the data, mark it with a timestamp, store it temporarily and ultimately pass it on to a PC. The data is then analyzed in the familiar PC environment.

Specification

Ethernet analysis tool

Ethernet analysis tool with up to 2 slots for hub expansion modules

Status indicators

Module status, bus function

Module status

Yes, using LED status indicator and software

Bus function

Yes, using LED status indicator and software

Power consumption

2 W

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

KC

Yes

Type

Ethernet analysis tool

Variant

2x shielded RJ45

Line length

Max. 100 m between 2 stations (segment length)

Transfer rate

100 Mbit/s

Physical layer

100BASE-TX

Half-duplex

Yes

Full-duplex

Yes

Autonegotiation

Yes

Auto-MDI/MDIX

Yes

Electrical isolation

POWERLINK (IF1, IF2) isolated from power supply

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 separately.
Order 1x bus base X20BB8x separately.

X20BB80

37.5+0.2 mm

X20BB81

62.5+0.2 mm

X20BB82

87.5+0.2 mm