Fast delivery within 72 Hours
B&R X20DO6322
6 digital outputsSource connection2-wire connectionsGND for signal supplyIntegrated output protection1-wire connection type with 6-pin terminal blockOSP mode…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
6 digital outputsSource connection2-wire connectionsGND for signal supplyIntegrated output protection1-wire connection type with 6-pin terminal blockOSP mode
This module is equipped with 6 outputs with 1- or 2-wire connections and GND for signal power supply. The outputs are designed for a source circuit. For continuous 1-wire wiring, the 6x X20 terminal block can be used. 2-wire wiring can be implemented with the 12x terminal block.
Specification
| I/O module |
6 digital outputs 24 VDC for 1- or 2-wire connections |
|---|---|
| B&R ID code |
0x1B98 |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Outputs |
Yes, using LED status indicator and software (output error status) |
| Bus |
0.18 W |
| Internal I/O |
0.71 W |
| Additional power dissipation caused by actuators (resistive) [W] |
+0.31 |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| DNV |
Temperature: B (0 to 55°C) |
| CCS |
Yes |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| BV |
EC33B |
| KC |
Yes |
| Variant |
Current-sourcing FET |
| Nominal voltage |
24 VDC |
| Switching voltage |
24 VDC -15% / +20% |
| Nominal output current |
0.5 A |
| Total nominal current |
3 A |
| Connection type |
1- or 2-wire connections |
| Output circuit |
Source |
| Output protection |
Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current") |
| Diagnostic status |
Output monitoring with 10 ms delay |
| Leakage current when the output is switched off |
5 µA |
| RDS(on) |
210 mΩ |
| Peak short-circuit current |
<12 A |
| Switch-on in the event of overload shutdown or short-circuit shutdown |
Approx. 10 ms (depends on the module temperature) |
| 0 → 1 |
<300 µs |
| 1 → 0 |
<300 µs |
| Resistive load |
Max. 500 Hz |
| Inductive load |
See section "Switching inductive loads". |
| Braking voltage when switching off inductive loads |
Typ. 50 VDC |
| Insulation voltage between channel and bus |
500 Veff |
| Electrical isolation |
Channel isolated from bus |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
– |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Note |
Order 1x terminal block X20TB06 or X20TB12 separately. |
| Pitch |
12.5+0.2 mm |

Reviews
Clear filtersThere are no reviews yet.