Fast delivery within 72 Hours

B&R X20DO4F49

4 digital outputsRelay module for 250 VDC / 240 VAC2 normally open contacts and 2 changeover contactsSingle-channel isolated outputs

This module is equippe…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 digital outputsRelay module for 250 VDC / 240 VAC2 normally open contacts and 2 changeover contactsSingle-channel isolated outputs

This module is equipped with 4 relay outputs (2 normally open and 2 changeover contacts each) for 250 VDC / 240 VAC. The outputs are single-channel isolated.

Specification

I/O module

4 digital outputs 250 VDC / 240 VAC, outputs single-channel isolated

B&R ID code

0xF76A

Status indicators

I/O function per channel, operating state, module status

Module run/error

Yes, using LED status indicator and software

Outputs

Yes, using LED status indicator

Bus

1.1 W

Internal I/O

Additional power dissipation caused by actuators (resistive) [W]

+0.32

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

Functional safety

IEC 61508 in preparation
EN 62061 in preparation
EN ISO 13849-1 in preparation
IEC 61511 in preparation

UL

cULus E115267
Industrial control equipment

DNV

Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)

CCS

Yes

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33B
Temperature: 5 – 55°C
Vibration: 4 g
EMC: Bridge and open deck

Variant

Relays: 2 normally open contacts and 2 changeover contacts
Channels are single-channel isolated.

Nominal voltage

250 VDC / 240 VAC

Max. voltage

250 VAC

Switching voltage

Max. 250 VDC / 250 VAC

Rated frequency

DC / 45 to 63 Hz

Nominal output current

DC: See section "DC switching capacity".
AC: 2 A at 240 VAC

Total nominal current

DC: See section "DC switching capacity".
AC: 8 A at 240 VAC

Actuator power supply

External

Inrush current

Max. 8 A (per channel)

Contact resistance

Max. 100 mΩ

0 → 1

Normally open contact ≤15 ms / Changeover contact ≤19 ms

1 → 0

Normally open contact ≤11 ms / Changeover contact ≤15 ms

Channel - Bus

Tested at 3500 VAC

Channel - Channel

Tested at 1700 VAC

Channel - Ground

Tested at 3500 VAC

Electrical

105 at 2 A (normally open contact and changeover contact)

Mechanical

30 x106 cycles (normally open contact and changeover contact)

Minimum

0.12 W DC / 2.4 W AC

Maximum

DC: See section "DC switching capacity".
AC: 480 W

Internal

None

AC

RC combination or VDR

DC

Inverse diode, RC combination or VDR

Electrical isolation

Channel isolated from channel, bus and I/O power supply

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB32 separately.
Order 1x bus module X20BM32 separately.

Pitch

25+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20DO4F49”

Your email address will not be published. Required fields are marked *