Fast delivery within 72 Hours
B&R X20DO2633
2 digital outputsOutputs with integrated snubber circuitOutputs with 48 to 240 VACL switchingZero-crossing detectionPhase-angle controlOpen-circuit detection for each channelNegative half-waves can be…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
2 digital outputsOutputs with integrated snubber circuitOutputs with 48 to 240 VACL switchingZero-crossing detectionPhase-angle controlOpen-circuit detection for each channelNegative half-waves can be switched off50 Hz or 60 Hz3-wire connections240 V codingOSP modeFrequency mode
The module is a digital output module with phase-angle control that is equipped with 2 Triac outputs using 3-line connections. The supply (L and N) is fed directly to the module.
Specification
| I/O module |
2 digital outputs 48 to 240 VAC for 3-wire connections |
|---|---|
| B&R ID code |
0xAC39 |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Outputs |
Yes, using LED status indicator and software |
| Bus |
0.6 W |
| Internal I/O |
– |
| External I/O |
– |
| Additional power dissipation caused by actuators (resistive) [W] |
+6 |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL |
cULus E115267Industrial control equipment |
| HazLoc |
cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| KC |
Yes |
| Variant |
Triac |
| Circuit |
L-switching |
| Nominal voltage |
48 to 240 VAC |
| Max. voltage |
264 VAC |
| Rated frequency |
47 to 63 Hz |
| Nominal output current |
2 A |
| Total nominal current |
4 A |
| Output current |
2.5 A |
| Summation current |
5 A |
| Connection type |
3-wire connections |
| Zero-crossing detection |
Yes |
| Minimum holding current IH |
15 mA |
| Leakage current |
Max. 2 mA at 240 V at 50 HzMax. 2.4 mA at 240 V at 60 Hz |
| Residual voltage (on-state voltage) |
1.5 V |
| Area |
5 to 95% |
| Resolution |
1% |
| Accuracy (60 to 240 VAC) |
<100 μs |
| Voltage monitoring L - N |
Yes |
| Additional functions |
Open-circuit detection |
| Overvoltage protection between L and N |
Yes, varistor |
| Channel - Bus |
Tested with 2300 VAC (Rev. <E0 1500 VAC) |
| Channel - Internal I/O |
Tested with 2300 VAC (Rev. <E0 2000 VAC) |
| Channel - Ground |
Tested with 2300 VAC (Rev. <E0 1500 VAC) |
| External |
See section "External fuses". |
| Internal |
Snubber circuit (RC element) and varistor |
| Electrical isolation |
Channel isolated from bus and I/O power supply |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Not permitted |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
See section "Derating". |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Note |
Order 1x terminal block X20TB32 separately.Order 1x bus module X20BM32 separately. |
| Pitch |
25+0.2 mm |

Reviews