B&R X20DC2396

2 ABR incremental encoder 24 V2 additional inputs e.g. for home enable switch24 VDC and GND for encoder supply

The module is equipped with two inputs for a…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

2 ABR incremental encoder 24 V2 additional inputs e.g. for home enable switch24 VDC and GND for encoder supply

The module is equipped with two inputs for an ABR incremental encoder with 24 V encoder signal.

Specification

I/O module

2 ABR incremental encoder 24 V

Input voltage

24 VDC -15% / +20%

B&R ID code

0x1BAB

Status indicators

I/O function per channel, operating state, module status

Module run/error

Yes, using LED status indicator and software

Bus

0.01 W

Internal I/O

1.5 W

Additional power dissipation caused by actuators (resistive) [W]

Type of signal lines

Shielded lines must be used for all signal lines.

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X

UL

cULus E115267Industrial control equipment

HazLoc

cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5

DNV

Temperature: B (0 to 55°C)Humidity: B (up to 100%)Vibration: B (4 g)EMC: B (bridge and open deck)

CCS

Yes

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33BTemperature: 5 – 55°CVibration: 4 gEMC: Bridge and open deck

KC

Yes

Quantity

2

Nominal voltage

24 VDC

Input current at 24 VDC

Approx. 1.3 mA

Input circuit

Sink

Hardware

≤2 µs

Software

Connection type

3-wire connections

Input resistance

18.4 kΩ

Additional functions

Home enable switch

Low

<5 VDC

High

>15 VDC

Insulation voltage between channel and bus

500 Veff

Encoder inputs

24 V, asymmetrical

Counter size

16/32-bit

Input frequency

Max. 100 kHz

Evaluation

4x

Encoder power supply

Module-internal, max. 600 mA

Overload characteristics of encoder power supply

Short-circuit proof, overload-proof

Insulation voltage between encoder and bus

500 Veff

Electrical isolation

Bus isolated from encoder and reference enable switchEncoder not isolated from reference enable switch and each other

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB12 separately.Order 1x bus module X20BM11 separately.

Pitch

12.5+0.2 mm