Fast delivery within 72 Hours
B&R X20cSO6530
6 safe relay outputsOutput type “Relay”Relay module for 230 VAC / 24 VDCSwitching current 6 ANormally open contactSingle-channel isolated outputs
This modu…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
6 safe relay outputsOutput type “Relay”Relay module for 230 VAC / 24 VDCSwitching current 6 ANormally open contactSingle-channel isolated outputs
This module is equipped with 6 safe relay outputs.The module can be used for controlling floating actuators in safety-related applications up to PL e or SIL 3.Safety relays are installed in the module. The positively driven feedback contacts are evaluated internally by the module. Safe digital output channels provide protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.
Specification
| I/O module |
6 relays with 1 normally open contact each, 230 VAC / 2 A (6 A), 24 VDC / 6 A |
|---|---|
| B&R ID code |
0x28DE |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Outputs |
Yes, using LED status indicator and software |
| Scope |
Module |
| Function |
Module functionality |
| Standalone mode |
No |
| Max. I/O cycle time |
1 ms |
| Bus |
0.26 W |
| Internal I/O |
1.65 W |
| Additional power dissipation caused by actuators (resistive) [W] |
4.32 |
| Channel - Bus |
Yes |
| Channel - Channel |
Yes |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| Functional safety |
IEC 61508:2010, SIL 3 |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| EN 50155 |
No |
| EN 61810-3 |
Yes |
| Note |
Order 1x safety-keyed terminal block separately. |
| Nominal voltage |
24 VDC |
| Voltage range |
24 VDC -15% / +20% |
| Integrated protective function |
Reverse polarity protection |
| Quantity |
6 |
| Variant |
Relay / Normally open contact, internal high-side and low-side control |
| Nominal output current |
5 mA to 6 A (hardware revision <B5: 2 A) |
| Diagnostic status |
Contact position determined by positively driven contacts |
| Max. switching frequency |
See section "Inrush current behavior for output channels". |
| 0 → 1 |
<50 ms |
| 1 → 0 |
<50 ms |
| Insulation voltage between channel and bus |
Safe disconnection of 300 VAC per EN 50178 |
| Insulation voltage between channel and channel |
Tested at 1350 VAC |
| Contact resistance (without terminal block) |
20 mΩ |
| Contact service life |
See "Contact service life". |
| Short-circuit/Overload protection |
External 6 A gL/gG fuse (melting fuse), LS automat C characteristic 1.6 A |
| Switching voltage range |
5 to 24 VDC, 5 to 230 VAC |
| Coil voltage |
24 VDC -15% / +20% |
| Short-circuit proof |
Yes, 1000 A (with specified short-circuit/overload protection) |
| Max. inrush current |
AC: 50 A for 100 ms, DC: 10 A for 200 ms |
| Overvoltage category per EN 60664-1 |
II |
| UL 508 |
B300 / R300 |
| Horizontal |
Yes |
| Vertical |
Yes |
| Installation elevation above sea level |
0 to 2000 m, no limitation |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
See section "Derating". |
| Starting temperature |
Yes, -25°C |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
Up to 100%, condensing |
| Pitch |
25+0.2 mm |

Reviews