Fast delivery within 72 Hours
 
					B&R X20cSC2432
2 safe digital inputs, sink circuit2 pulse outputsSoftware input filter configurable for each channel2 safe relay outputsOutput type “Relay”Relay module for 48 VAC / 24 VDCSwitching current 6 ANormall…
Shipping & Delivery
- 
Courier delivery 
Our courier will deliver to the specified address
2-3 Days
From $20
- 
DHL Courier delivery 
DHL courier will deliver to the specified address
2-3 Days
From $40
- 
Warranty 1 year 
- 
Free 30-Day returns 
Description
2 safe digital inputs, sink circuit2 pulse outputsSoftware input filter configurable for each channel2 safe relay outputsOutput type “Relay”Relay module for 48 VAC / 24 VDCSwitching current 6 ANormally open contactSingle-channel isolated outputs
The module is equipped with 2 safe digital inputs and 2 safe relay outputs. It is designed for a nominal voltage of 24 VDC.The module can be used to read digital signals and for floating control of actuators in safety-related applications up to PL e or SIL 3.The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.Safety relays are installed in the module. The positively driven feedback contacts are evaluated internally by the module. Safe digital output channels provide protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.
Specification
| I/O module | 2 safe type A digital inputs, 2 pulse outputs, 24 VDC, 2 relays with 1 normally open contact each, 48 VAC / 6 A, 24 VDC / 6 A | 
|---|---|
| B&R ID code | 0xDD5D | 
| Status indicators | I/O function per channel, operating state, module status | 
| Module run/error | Yes, using LED status indicator and software | 
| Outputs | Yes, using LED status indicator and software | 
| Inputs | Yes, using LED status indicator and software | 
| Scope | Module | 
| Function | Module functionality | 
| Standalone mode | No | 
| Max. I/O cycle time | 1 ms | 
| Bus | 0.26 W | 
| Internal I/O | 1.15 W | 
| Relay outputs | 1.44 | 
| Pulse outputs | 0.1 | 
| Channel - Bus | Yes | 
| Channel - Channel | Yes | 
| CE | Yes | 
| UKCA | Yes | 
| CRA (Cyber Resilience Act) | In preparation | 
| Functional safety | EN 50156-1:2004 | 
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc | 
| UL | cULus E115267 | 
| HazLoc | cCSAus 244665 | 
| DNV | Temperature: A (0 to 45°C) | 
| LR | ENV1 | 
| KR | Yes | 
| ABS | Yes | 
| BV | EC21B | 
| EN 50155 | Yes | 
| EN 61810-3 | Yes | 
| Note | Order 1x safety-keyed terminal block separately. | 
| Nominal voltage | 24 VDC | 
| Voltage range | 24 VDC -15% / +20% | 
| Integrated protective function | Reverse polarity protection | 
| Quantity | 2 | 
| Variant | Push-Pull | 
| Input characteristics per EN 61131-2 | Type 1 | 
| Hardware | ≤150 μs | 
| Software | Configurable between 0 and 500 ms | 
| Input circuit | Sink | 
| Input voltage | 24 VDC -15% / +20% | 
| Input current at 24 VDC | Min. 2 mA to max. 4.59 mA | 
| Input resistance | Min. 5.23 kΩ | 
| Error detection time | 100 ms | 
| Insulation voltage between channel and bus | Safe disconnection of 300 VAC per EN 50178 | 
| Low | <5 VDC | 
| High | >15 VDC | 
| Line length between signal source (pulse output or external signal) and input | Max. 60 m with unshielded line | 
| Nominal output current | 50 mA | 
| Diagnostic status | Contact position determined by positively driven contacts | 
| Max. switching frequency | See section "Inrush current behavior for output channels". | 
| 0 → 1 | <50 ms | 
| 1 → 0 | <50 ms | 
| Insulation voltage between channel and channel | 48 VAC | 
| Contact resistance (without terminal block) | 20 mΩ | 
| Contact service life | See "Contact service life". | 
| Short-circuit/Overload protection | External 6 A gL/gG fuse (melting fuse), LS automat C characteristic 1.6 A | 
| Switching voltage range | 5 to 24 VDC, 5 to 48 VAC | 
| Coil voltage | 24 VDC -15% / +20% | 
| Short-circuit proof | Yes, 1000 A (with specified short-circuit/overload protection) | 
| Max. inrush current | 30 A for 20 ms | 
| Overvoltage category per EN 60664-1 | II | 
| AC1 | 48 VAC / 6 A | 
| AC15 | 48 VAC / 3 A | 
| DC1 | 24 VDC / 6 A | 
| DC13 | 24 VDC / 5 A / 0.1 Hz | 
| UL 508 | B300 / R300 | 
| Output protection | Shutdown of individual channels in the event of overload or short circuit | 
| Peak short-circuit current | 25 A for 5 ms | 
| Short-circuit current | 1.4 Aeff | 
| Leakage current when the output is switched off | 0.1 mA | 
| RDS(on) | 20 Ω | 
| Switching voltage | I/O power supply minus voltage drop due to RDS(on) | 
| Total nominal current | 100 mA | 
| Horizontal | Yes | 
| Vertical | Yes | 
| Installation elevation above sea level | 0 to 2000 m, no limitation | 
| Degree of protection per EN 60529 | IP20 | 
| Horizontal mounting orientation | -25 to 60°C | 
| Vertical mounting orientation | -25 to 50°C | 
| Derating | See section "Derating". | 
| Starting temperature | Yes, -25°C | 
| Storage | 5 to 95%, non-condensing | 
| Transport | 5 to 95%, non-condensing | 
| Operation | Up to 100%, condensing | 
| Pitch | 25+0.2 mm | 
 
	 
	 
				 
				
 
		 
		 
		 
		 
		 
		 
		
Reviews