B&R X20CMR100

Measurement and evaluation of the ambient conditions in the control cabinetRecording ambient conditionsRecording operating hours and power-on cyclesTechnology Guarding directly on the moduleSupports b…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Measurement and evaluation of the ambient conditions in the control cabinetRecording ambient conditionsRecording operating hours and power-on cyclesTechnology Guarding directly on the moduleSupports blackout mode

The module is designed for measuring ambient conditions in the control cabinet as well as recording operating hours and power-on cycles. In addition, the module is equipped with a Technology Guard and supports blackout mode.Measuring and evaluating ambient conditionsThe ambient conditions are continuously evaluated by the module. The duration in which individual parameters are within certain ranges is stored internally. This makes it possible, for example, to determine how long the system remained in a certain temperature range. The histograms recorded by the module can be read out by the user.Technology GuardingWith the integrated Technology Guard, it is possible to implement license protection directly via the module instead of the USB dongle. The same functions can be used as with the USB dongle.Blackout modeThe integrated blackout mode ensures that module functionality is maintained even in the event of network failure.

Specification

I/O moduleMeasurement of ambient conditions: Internal module temperature, relative humidity, operating hours, power-on cycles
B&R ID code0xF1AD
Status indicatorsMemory access, operating state, module status
Module run/errorYes, using LED status indicator and software
ScopeModule
FunctionModule functionality
Standalone modeNo
Bus0.4 W
Internal I/O
Additional power dissipation caused by actuators (resistive) [W]
Data retention10 years at room temperature
Guaranteed erase/write cyclesUp to 10 million
Application memory241 bytes customized data
Coding128-bit AES, SHA-256, 2048-bit RSA, 224-bit ECC
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ULcULus E115267 Industrial control equipment
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck
Sensor positionModule-internal
Sampling rate1 s
Measurement range5 to 95%
Resolution1%/LSB
Max. error±2% at 10 to 80% relative humidity ±3% at 80% relative humidity
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.