Measurement and evaluation of the ambient conditions in the control cabinetRecording ambient conditionsRecording operating hours and power-on cyclesSaving user data directly on the moduleSupports blac…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
Measurement and evaluation of the ambient conditions in the control cabinetRecording ambient conditionsRecording operating hours and power-on cyclesSaving user data directly on the moduleSupports blackout mode
The module is designed for measuring ambient conditions in the control cabinet as well as recording operating hours and power-on cycles. In addition, the module offers the option of storing user data directly on the module and supports blackout mode.Measuring and evaluating ambient conditionsThe ambient conditions are continuously evaluated by the module. The duration in which individual parameters are within certain ranges is stored internally. This makes it possible, for example, to determine how long the system remained in a certain temperature range. The histograms recorded by the module can be read out by the user.Internal module memory for user dataWith 512 kB nonvolatile user memory (flash), data from the application can be saved directly on the module and also read back from the module. The data is therefore retained after the module or CPU is restarted and remains with the module in the event that the module is connected to another machine or system, for example. Data retention is maintenance-free – without batteries.Blackout modeThe integrated blackout mode ensures that module functionality is maintained even in the event of network failure.
Specification
| I/O module |
Measurement of ambient conditions: |
|---|---|
| B&R ID code |
0xF1AC |
| Status indicators |
Memory access, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Scope |
Module |
| Function |
Module functionality |
| Standalone mode |
No |
| Bus |
0.4 W |
| Internal I/O |
– |
| Additional power dissipation caused by actuators (resistive) [W] |
– |
| Type |
512 kB flash memory |
| Sectors |
8 sectors, 64 kB each |
| Data retention |
20 years at 55°C |
| Guaranteed erase/write cycles |
100,000 per sector |
| Error-correcting code (ECC) |
No |
| Write protection |
No |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| UL |
cULus E115267 |
| DNV |
Temperature: B (0 to 55°C) |
| CCS |
Yes |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| Sensor position |
Module-internal |
| Sampling rate |
1 s |
| Measurement range |
5 to 95% |
| Resolution |
1%/LSB |
| Max. error |
±2% at 10 to 80% relative humidity |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
– |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Note |
Order 1x terminal block X20TB12 separately. |
| Pitch |
12.5+0.2 mm |