Fast delivery within 72 Hours

B&R X20CM8281

Digital and analog channelsSelectable current and voltage for AI and AOCounter functions

The module is a universal mixed module. On this module, digital I/…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Digital and analog channelsSelectable current and voltage for AI and AOCounter functions

The module is a universal mixed module. On this module, digital I/O and analog I/O are combined. A current or voltage signal can be used for the analog I/O as desired. Counter functions on two of the digital inputs expand the range of use.

Specification

I/O module

4 digital inputs, 2 digital outputs, 1 analog input, 1 analog output, special functions

B&R ID code

0x24C3

Status indicators

I/O function per channel, operating state, module status

Module run/error

Yes, using LED status indicator and software

Analog inputs

Yes, using LED status indicator and software

Digital outputs

Yes, using LED status indicator and software (output error status)

Bus

0.01 W

Internal I/O

1.75 W

Additional power dissipation caused by actuators (resistive) [W]

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

DNV

Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)

CCS

Yes

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33B
Temperature: 5 – 55°C
Vibration: 4 g
EMC: Bridge and open deck

KC

Yes

Quantity

1

Nominal voltage

24 VDC

Input characteristics per EN 61131-2

Type 1

Input voltage

24 VDC -15% / +20%

Input current at 24 VDC

Typ. 3.3 mA

Input circuit

Sink

Hardware

≤2 µs

Software

Default 1 ms, configurable between 0 and 25 ms in 0.2 ms increments

Connection type

1-wire connections

Input resistance

Typ. 7.18 kΩ

Additional functions

20 kHz event counting, gate measurement

Low

<5 VDC

High

>15 VDC

Insulation voltage between channel and bus

500 Veff

Signal form

Square wave pulse

Evaluation

Positive edge – Negative edge

Input frequency

Max. 20 kHz

Counter 1

Input 1

Counter 2

Input 3

Counter frequency

Max. 20 kHz

Counter size

16-bit

Internal

48 MHz, 24 MHz, 12 MHz, 6 MHz, 3 MHz, 1.5 MHz, 750 kHz, 375 kHz, 187.5 kHz

Length of pause between pulses

≥100 µs

Pulse length

≥20 µs

Supported inputs

Input 4

Input

±10 V or 0 to 20 mA / 4 to 20 mA, via different terminal connections

Input type

Single-ended

Voltage

Max. 0.02%, from 10 MΩ → 1 kΩ, resistive

Current

Max. 0.5%, from 1 Ω → 400 Ω, resistive

Conversion time

300 µs, conversion runs asynchronous to the X2X Link cycle

Output format

INT

Input protection

Protection against wiring with supply voltage

Conversion procedure

Successive approximation

Input filter

Second-order low-pass filter / Cutoff frequency 1 kHz

Gain

0.05%

Offset

0.125%

Variant

Current-sourcing FET

Switching voltage

24 VDC -15% / +20%

Nominal output current

0.5 A

Total nominal current

1 A

Output circuit

Source

Output protection

Short-circuit proof

Diagnostic status

Output monitoring with 10 ms delay

Leakage current when the output is switched off

5 µA

RDS(on)

105 mΩ

Peak short-circuit current

<14 A

Switch-on in the event of overload shutdown or short-circuit shutdown

Approx. 10 ms (depends on the module temperature)

0 → 1

<250 µs

1 → 0

<270 µs

Resistive load

Max. 100 Hz

Inductive load

See section "Switching inductive loads".

Braking voltage when switching off inductive loads

Typ. 50 VDC

Output

±10 V or 0 to 20 mA, via different terminal connections

Digital converter resolution

12-bit

Settling time on output change over entire range

1 ms

Switch on/off behavior

Internal enable relay for startup and errors

Nonlinearity

<0.1%

Electrical isolation

Channel isolated from bus

Channel not isolated from channel

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

See section "Derating".

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.

Pitch

12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20CM8281”

Your email address will not be published. Required fields are marked *