Fast delivery within 72 Hours

B&R X20cDC1196

1 ABR incremental encoder 5 V2 additional inputs e.g. for home enable switch5 VDC, 24 VDC and GND for encoder supply

The module is equipped with 1 input fo…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

1 ABR incremental encoder 5 V2 additional inputs e.g. for home enable switch5 VDC, 24 VDC and GND for encoder supply

The module is equipped with 1 input for an ABR incremental encoder with 5 V encoder signal.

Specification

I/O module

1 ABR incremental encoder 5 V

B&R ID code

0xEB54

Status indicators

I/O function per channel, operating state, module status

Module run/error

Yes, using LED status indicator and software

Bus

0.01 W

Internal I/O

1.5 W

Additional power dissipation caused by actuators (resistive) [W]

Type of signal lines

Shielded lines must be used for all signal lines.

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

DNV

Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33B
Temperature: 5 – 55°C
Vibration: 4 g
EMC: Bridge and open deck

Quantity

2

Nominal voltage

24 VDC

Input characteristics per EN 61131-2

Type 1

Input voltage

24 VDC -15% / +20%

Input current at 24 VDC

Approx. 3.3 mA

Input circuit

Sink

Hardware

≤200 ns

Software

Connection type

3-wire connections

Input resistance

7.19 kΩ

Additional functions

Home enable switch

Low

<5 VDC

High

>15 VDC

Insulation voltage between channel and bus

500 Veff

Encoder inputs

5 V, symmetrical

Counter size

16/32-bit

Input frequency

Max. 600 kHz

Evaluation

4x

5 VDC

±5%, module-internal, max. 300 mA

24 VDC

Module-internal, max. 300 mA

Common-mode range

-7 V ≤ VCM ≤ +12 V

Overload characteristics of encoder power supply

Short-circuit proof, overload-proof

Insulation voltage between encoder and bus

500 Veff

Electrical isolation

Bus isolated from encoder and channel

Channel not isolated from channel and encoder

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Starting temperature

Yes, -40°C

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

Up to 100%, condensing

Note

Order 1x terminal block X20TB12 separately.
Order 1x bus module X20cBM11 separately.