Fast delivery within 72 Hours

B&R X20BC0088

Fieldbus: EtherNet/IPIntegrated 3-port switch for efficient cablingAuto-configuration of I/O modulesCan be configured by the scanner (master) using configuration assemblyWeb interfaceDHCP-capableConfi…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Fieldbus: EtherNet/IPIntegrated 3-port switch for efficient cablingAuto-configuration of I/O modulesCan be configured by the scanner (master) using configuration assemblyWeb interfaceDHCP-capableConfigurable I/O cycle (0.5 to 4 ms)Minimum fieldbus cycle time (also requested packet interval or RPI): 1 ms

EtherNet/IP is an Ethernet-based fieldbus. EtherNet/IP was developed by Allen-Bradley (Rockwell Automation) and later transferred to the Open DeviceNet Vendor Association (ODVA) as an open standard. In 1998, a working group at ControlNet International developed a procedure for setting the published Common Industrial Protocol to Ethernet. EtherNet/IP was published in March 2000 as an open industrial automation standard based on this procedure. This bus controller makes it possible to connect X2X Link I/O nodes to EtherNet/IP. The bus controller can be operated via interface module X20IF10D1-1 or by 3rd-party systems with EtherNet/IP scanner functionality.With multifunction modules, the bus controller supports only the default function model in the event of automatic configuration by the bus controller (see the respective module description). Automation Studio V4.3 or later can be used to easily create configuration files (e.g. EDS files, binary files). All other function models are also supported by transferring configuration data to the bus controller (e.g. using the scanner via a “configuration assembly”). Automation Studio can be downloaded at no cost from the B&R website (www.br-automation.com). The evaluation license is permitted to be used to create complete configurations for fieldbus bus controllers at no cost.

Specification

Bus controller

EtherNet/IP adapter (slave)

B&R ID code

0x26D8

Status indicators

Module status, network status, bus function

Module status

Yes, using LED status indicator and software

Bus function

Yes, using LED status indicator and software

Network status

Yes, using LED status indicator and software

Bus

2 W

Additional power dissipation caused by actuators (resistive) [W]

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

KC

Yes

Fieldbus

1 ms

Variant

2x shielded RJ45 (switch)

Line length

Max. 100 m between 2 stations (segment length)

Transfer rate

10/100 Mbit/s

Physical layer

10BASE-T/100BASE-TX

Half-duplex

Yes

Full-duplex

Yes

Autonegotiation

Yes

Auto-MDI/MDIX

Yes

Synchronization between bus systems possible

No

Electrical isolation

EtherNet/IP isolated from bus and I/O

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 or X20PS9402 separately.
Order 1x bus base X20BB80 separately.

Pitch

37.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20BC0088”

Your email address will not be published. Required fields are marked *