Fast delivery within 72 Hours
B&R X20ATC402
6 channels for thermocouplesFor sensor types J, K, N, S, B, R, E, C, T, raw value measurementIntegrated terminal temperature compensation2x PT1000 sensor integrated in the terminal (X20TB1E)2x externa…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
6 channels for thermocouplesFor sensor types J, K, N, S, B, R, E, C, T, raw value measurementIntegrated terminal temperature compensation2x PT1000 sensor integrated in the terminal (X20TB1E)2x external PT1000 sensor can be connected (X20TB1F)Configurable filter timeConfigurable resolutionNetTime timestamp: Moment of measurement
The module is equipped with 6 inputs for J, K, N, S, B, R, E, C and T thermocouple sensors.This module can also be equipped with the X20TB1E thermocouple terminal block with integrated PT1000 temperature sensors. This makes it possible to achieve optimal terminal temperature compensation.
Specification
| I/O module |
6 inputs for thermocouples |
|---|---|
| B&R ID code |
0xBB99 |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Inputs |
Yes, using LED status indicator and software |
| Bus |
0.01 W |
| Internal I/O |
0.85 W |
| Additional power dissipation caused by actuators (resistive) [W] |
– |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| DNV |
Temperature: B (0 to 55°C) |
| CCS |
Yes |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| BV |
EC33B |
| KC |
Yes |
| Input |
Thermocouple |
| Digital converter resolution |
16-bit |
| Filter time |
Configurable between 1 and 200 ms |
| N channels |
(n + 2) * 4 * x ms |
| 1 channel |
x ms |
| Output format |
INT |
| Type J: Fe-CuNi |
±0.0033 %/°C |
| Type K: NiCr-Ni |
±0.0042 %/°C |
| Type N: NiCrSi-NiSi |
±0.0048 %/°C |
| Type S: PtRh10-Pt |
±0.0123 %/°C |
| Type B: PtRh30-PtRh6 |
±0.0166 %/°C |
| Type R: PtRh13-Pt |
±0.0109 %/°C |
| Type E: NiCr-CuNi |
±0.003 %/°C |
| Type C: WRe5-WRe26 |
±0.0062 %/°C |
| Type T: Cu-CuNi |
±0.011%/°C |
| Terminal temperature |
±0.004% |
| Voltage |
±0.003 %/°C |
| Sensor standard |
EN 60584 |
| Sensor temperature |
1 LSB = 0.1°C or 0.01°C |
| Range undershoot |
0x8001 or 0x80000001 |
| Range overshoot |
0x7FFF or 0x7FFFFFFF |
| Open circuit |
0x7FFF or 0x7FFFFFFF |
| Open inputs |
0x7FFF or 0x7FFFFFFF |
| General fault |
0x8000 or 0x80000000 |
| Conversion procedure |
Sigma-delta |
| Linearization method |
Internal |
| Permissible input signal |
Max. ±15 V |
| Input filter |
First-order low-pass filter / cutoff frequency 500 Hz |
| Gain |
±0.04% |
| Channel |
±0.004% |
| Operating modes |
Internal/remote or external |
| Basic accuracy at 25°C not taking Pt1000 sensor into account |
±0.06% |
| With natural convection |
±1.5°C after 20 min |
| With artificial convection |
±3°C after 20 min |
| DC |
>100 dB |
| 50 Hz |
>100 dB |
| 60 Hz |
>100 dB |
| Common-mode range |
±14 V |
| Crosstalk between channels |
<-70 dB |
| Between channel and bus |
500 Veff |
| Electrical isolation |
Channel isolated from bus |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
– |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Note |
Order 1x terminal block X20TB1E for internal/remote terminal temperature compensation separately. |
| Pitch |
12.5+0.2 mm |

Reviews