Fast delivery within 72 Hours

B&R X20ATB312

4 inputs for resistance temperature measurementPT100 sensorDirect resistance measurement as well4-wire measurementFilter time can be configuredNetTime timestamp: Moment of measurement…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 inputs for resistance temperature measurementPT100 sensorDirect resistance measurement as well4-wire measurementFilter time can be configuredNetTime timestamp: Moment of measurement

The module is equipped with 4 inputs for PT100 4-line resistance temperature measurement.

Specification

I/O module

4 inputs for Pt100 resistance temperature measurement

B&R ID code

0xE0EF

Status indicators

I/O function per channel, operating state, module status

Module run/error

Yes, using LED status indicator and software

Inputs

Yes, using LED status indicator and software

Bus

0.01 W

Internal I/O

0.5 W (Rev. ≥D0), 0.6 W (Rev. <D0)

Additional power dissipation caused by actuators (resistive) [W]

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

DNV

Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)

CCS

Yes

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33B
Temperature: 5 – 55°C
Vibration: 4 g
EMC: Bridge and open deck

Input

Resistance measurement with constant current supply for 4-wire connections

Digital converter resolution

24-bit

Filter time

Configurable between 1 and 200 ms

1 channel

20 ms with 50 Hz filter

2 channels

40 ms per channel with 50 Hz filter

Conversion procedure

Sigma-delta

Output format

DINT or UDINT for resistance measurement

Temperature measurement range

-200 to 850°C

Resistance measurement range

0.5 to 390 Ω

Temperature sensor resolution

1 LSB = 0.01°C

Resistance measurement resolution

0.001 Ω

Input filter

First-order low-pass filter / cutoff frequency 1050 Hz

Sensor standard

EN 60751

Insulation voltage between channel and bus

500 Veff

Linearization method

Internal

Measuring current

1 mA

Temperature sensor normalization

-200.0 to 850.0°C

Reference

1568 Ω ±0.1%

Permissible input signal

Short-term max. 28.8 V

Gain

±0.0059%

Offset

±0.0015%

Max. gain drift

±0.00065%/°C

Max. offset drift

±0.000025%/°C

Nonlinearity

<0.001%

Standardized range of values for resistance measurement

19 to 390 Ω

Range undershoot

0x80000001

Range overshoot

0xFFFFFFFF

Open circuit

0xFFFFFFFF

General fault

0x80000000

Open inputs

0x7FFFFFFF

Electrical isolation

Channel isolated from bus
Channel not isolated from channel

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB1F separately.
Order 1x bus module X20BM11 separately.

Pitch

12.5+0.2 mm