Fast delivery within 72 Hours

B&R X20ATB312

4 inputs for resistance temperature measurementPT100 sensorDirect resistance measurement as well4-wire measurementFilter time can be configuredNetTime timestamp: Moment of measurement…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 inputs for resistance temperature measurementPT100 sensorDirect resistance measurement as well4-wire measurementFilter time can be configuredNetTime timestamp: Moment of measurement

The module is equipped with 4 inputs for PT100 4-line resistance temperature measurement.

Specification

I/O module4 inputs for Pt100 resistance temperature measurement
B&R ID code0xE0EF
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
Bus0.01 W
Internal I/O0.5 W (Rev. ≥D0), 0.6 W (Rev. <D0)
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck
InputResistance measurement with constant current supply for 4-wire connections
Digital converter resolution24-bit
Filter timeConfigurable between 1 and 200 ms
1 channel20 ms with 50 Hz filter
2 channels40 ms per channel with 50 Hz filter
Conversion procedureSigma-delta
Output formatDINT or UDINT for resistance measurement
Temperature measurement range-200 to 850°C
Resistance measurement range0.5 to 390 Ω
Temperature sensor resolution1 LSB = 0.01°C
Resistance measurement resolution0.001 Ω
Input filterFirst-order low-pass filter / cutoff frequency 1050 Hz
Sensor standardEN 60751
Insulation voltage between channel and bus500 Veff
Linearization methodInternal
Measuring current1 mA
Temperature sensor normalization-200.0 to 850.0°C
Reference1568 Ω ±0.1%
Permissible input signalShort-term max. 28.8 V
Gain±0.0059%
Offset±0.0015%
Max. gain drift±0.00065%/°C
Max. offset drift±0.000025%/°C
Nonlinearity<0.001%
Standardized range of values for resistance measurement19 to 390 Ω
Range undershoot0x80000001
Range overshoot0xFFFFFFFF
Open circuit0xFFFFFFFF
General fault0x80000000
Open inputs0x7FFFFFFF
Electrical isolationChannel isolated from bus Channel not isolated from channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB1F separately. Order 1x bus module X20BM11 separately.
Pitch12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20ATB312”

Your email address will not be published. Required fields are marked *