Fast delivery within 72 Hours

B&R X20AT2402

 270,30

2 inputs for thermocouplesFor sensor types J, K, N, S, B, RAdditional direct raw value measurementIntegrated terminal temperature compensationConfigurable filter timeConfigurable resolution…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

2 inputs for thermocouplesFor sensor types J, K, N, S, B, RAdditional direct raw value measurementIntegrated terminal temperature compensationConfigurable filter timeConfigurable resolution

The module is equipped with 2 inputs for J, K, N, S, B and R thermocouple sensors. The module has an integrated terminal temperature compensation. This module is designed for X20 6-pin terminal blocks. If needed (e.g. for logistical reasons), the 12-pin terminal block can also be used.

Specification

I/O module2 inputs for thermocouples
B&R ID code0x1BA8
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
Bus0.01 W
Internal I/O0.72 W
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user’s manual)FTZÚ 09 ATEX 0083X
ULcULus E115267Industrial control equipment
HazLoccCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C)Humidity: B (up to 100%)Vibration: B (4 g)EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC33BTemperature: 5 – 55°CVibration: 4 gEMC: Bridge and open deck
KCYes
InputThermocouple
Digital converter resolution16-bit
Filter timeConfigurable between 1 ms and 66.7 ms
1 channel80.4 ms with 50 Hz filter
2 channels120.6 ms with 50 Hz filter
Output formatINT
Type J: Fe-CuNi±0.0019 %/°C
Type K: NiCr-Ni±0.0024% / °C
Type N: NiCrSi-NiSi-270 to 1300°C (Rev. ≥D0)
Type S: PtRh10-Pt±0.0079 %/°C
Type B: PtRh30-PtRh6±0.0114 %/°C
Type R: PtRh13-Pt±0.0074 %/°C
Terminal temperature-25.0 to 85.0°C or -25.00 to 85.00°C
Raw value±65.534 mV
Terminal temperature compensationInternal
Sensor standardEN 60584
Sensor temperature1 LSB = 0.1°C or 0.01°C
Raw value output with respect to gain1 LSB = 1 µV or 2 µV
Type N (Rev. ≥D0)±0.0029 %/°C
Range undershoot0x8001
Range overshoot0x7FFF
Open circuit0x7FFF
Open inputs0x7FFF
General fault0x8000
Conversion procedureSigma-delta
Linearization methodInternal
Permissible input signalMax. ±5 V
Input filterFirst-order low-pass filter / cutoff frequency 500 Hz
Gain±0.06%
Max. gain drift±0.01%/°C
Nonlinearity±0.001%
DC>70 dB
50 Hz>70 dB
Common-mode range±15 V
Crosstalk between channels<-70 dB
Between channel and bus500 Veff
With artificial convection±4°C after 10 min
With natural convection±2°C after 10 min
Electrical isolationChannel isolated from busChannel not isolated from channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation0 to 55°C
Vertical mounting orientation0 to 50°C
Derating
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB06 or X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5+0.2 mm
ConditionNew
RevisionRev. I0, Rev. K0

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20AT2402”