B&R X20AP3132
Calculates RMS values from currents and voltagesCalculates active, reactive and apparent powerPhasing detectionMeasures individual phases and calculates cumulative valuesOptional measurement of curren…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
Calculates RMS values from currents and voltagesCalculates active, reactive and apparent powerPhasing detectionMeasures individual phases and calculates cumulative valuesOptional measurement of current through the neutral conductorCalculates frequency and harmonics with high precisionNetTime timestamp: Moment when measured value groups are read
Power monitoringThese modules measure active, reactive and apparent power individually for each of the 3 phases as well as all of them collectively. The power consumption of each phase is also recorded individually and in total. In addition, the modules provide the RMS values for voltage and current on the 3 phases. When measuring the current, the value of the current through the neutral conductor can also be detected and monitored. Measurement of the mains frequency and the phase angle of the 3 phases (current and voltage) complete the power measurement data.Energy managementThe integrated functions on the modules map the immediate power requirements of the machine in detail as well as record its total power consumption. For the user, all relevant data is prepared and made available in the process image.The ability to measure currents and voltages up to the 31st harmonic enables higher precision recording of RMS values than is generally possible. This allows the modules to easily cope with irregular sine curves and makes them well-suited to renewable energy applications. In these types of applications, for example, being able to accurately measure the frequency at a resolution of 0.01 Hz between 45 and 65 Hz is a great advantage. In general, the modules are suitable for use with 1-phase, 2-phase or 3-phase networks.NetTime timestamp of readout momentsFor many applications, not only the measured value is important, but also the exact moment when a group of measured values is read out. The module is equipped with a NetTime timestamp function for this that supplies a timestamp for the recorded position and trigger time with microsecond accuracy.The timestamp function is based on synchronized timers. If a timestamp event occurs, the module immediately saves the current NetTime. After the respective data is transferred to the CPU, including this precise moment, the CPU can then evaluate the data using its own NetTime (or system time), if necessary.
Specification
| I/O module |
3-phase power and energy metering module for current transformers, groundable on one side |
|---|---|
| B&R ID code |
0xE7C0 |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Inputs |
Yes, using LED status indicator and software |
| Bus |
0.85 W (Rev. <C0) |
| Internal I/O |
– |
| Additional module power dissipation [W] |
2 W |
| Voltage inputs - Current inputs |
Tested at 1300 VAC, 1 min |
| Inputs - Bus / I/O power supply |
Tested at 5500 VDC, 1 min |
| Inputs - Ground |
Tested at 5500 VDC, 1 min |
| Bus / I/O power supply - Ground |
Tested at 510 VAC, 1 min |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| Number of phases |
3 |
| Input impedance |
1.68 MΩ |
| Measurement category |
CAT II |
| Between phases |
Max. 480 VAC |
| Phase to N |
Max. 277 VAC |
| Max. display value |
655 VAC |
| Resolution |
1 mA, based on the primary current |
| Rated frequency |
50 and 60 Hz |
| Measurement range |
45 to 65 Hz |
| Quantity |
4 AC inputs |
| Secondary |
5 A |
| Primary |
65 A directly configurable, larger values through conversion in the application |
| Max. overload current |
8 x IN for 0.5 s |
| Max. measuring current |
5 A |
| Load |
20 mΩ |
| URMS |
±0.65% |
| IRMS |
±0.65% |
| Effective, reactive and apparent power |
±0.80% |
| Frequency, power factor and phase angle |
±0.50% |
| Active energy per phase and total |
±0.40% |
| Active energy of fundamental frequency per phase and total |
±0.50% |
| Active energy of harmonics per phase and total |
±0.80% |
| Reactive energy per phase and total |
±0.50% |
| Per phase and arithmetic total |
±0.50% |
| Vector sum |
±0.80% |
| Electrical isolation |
Channel isolated from bus |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Not permitted |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
– |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Note |
Order 1x terminal block X20TB32 separately. |
| Pitch |
25+0.2 mm |