Fast delivery within 72 Hours

B&R X20AP3121

Calculates RMS values from currents and voltagesCalculates active, reactive and apparent powerPhasing detectionMeasures individual phases and calculates cumulative valuesOptional measurement of curren…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Calculates RMS values from currents and voltagesCalculates active, reactive and apparent powerPhasing detectionMeasures individual phases and calculates cumulative valuesOptional measurement of current through the neutral conductorCalculates frequency and harmonics with high precisionNetTime timestamp: Moment when measured value groups are read

Power monitoringThese modules measure active, reactive and apparent power individually for each of the 3 phases as well as all of them collectively. The power consumption of each phase is also recorded individually and in total. In addition, the modules provide the RMS values for voltage and current on the 3 phases. When measuring the current, the value of the current through the neutral conductor can also be detected and monitored. Measurement of the mains frequency and the phase angle of the 3 phases (current and voltage) complete the power measurement data.Energy managementThe integrated functions on the modules map the immediate power requirements of the machine in detail as well as record its total power consumption. For the user, all relevant data is prepared and made available in the process image.The ability to measure currents and voltages up to the 31st harmonic enables higher precision recording of RMS values than is generally possible. This allows the modules to easily cope with irregular sine curves and makes them well-suited to renewable energy applications. In these types of applications, for example, being able to accurately measure the frequency at a resolution of 0.01 Hz between 45 and 65 Hz is a great advantage. In general, the modules are suitable for use with 1-phase, 2-phase or 3-phase networks.NetTime timestamp of readout momentsFor many applications, not only the measured value is important, but also the exact moment when a group of measured values is read out. The module is equipped with a NetTime timestamp function for this that supplies a timestamp for the recorded position and trigger time with microsecond accuracy.The timestamp function is based on synchronized timers. If a timestamp event occurs, the module immediately saves the current NetTime. After the respective data is transferred to the CPU, including this precise moment, the CPU can then evaluate the data using its own NetTime (or system time), if necessary.

Specification

I/O module

3-phase power and energy metering module for current transformers

B&R ID code

0xC9DB

Status indicators

I/O function per channel, operating state, module status

Module run/error

Yes, using LED status indicator and software

Inputs

Yes, using LED status indicator and software

Bus

0.85 W (Rev. <D0)
0.50 W (Rev. =D0)
0.45 W (Rev. >D0)

Internal I/O

Additional module power dissipation [W]

2 W

Inputs - Bus / I/O power supply

Tested at 5500 VDC, 1 min

Inputs - Ground

Tested at 5500 VDC, 1 min

Bus / I/O power supply - Ground

Tested at 510 VAC, 1 min

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

DNV

Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)

CCS

Yes

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33B
Temperature: 5 – 55°C
Vibration: 4 g
EMC: Bridge and open deck

Number of phases

3

Input impedance

1.68 MΩ

Between phases

Max. 480 VAC

Phase to N

Max. 277 VAC

Max. display value

655 VAC

Resolution

1 mA, based on the primary current

Rated frequency

50 and 60 Hz

Measurement range

45 to 65 Hz

Quantity

4 AC inputs

Secondary

1 A

Primary

65 A directly configurable, larger values through conversion in the application

Max. overload current

8 x IN for 0.5 s

Max. measuring current

1 A

Load

500 mΩ

URMS

±0.65%

IRMS

±0.65%

Effective, reactive and apparent power

±0.80%

Frequency, power factor and phase angle

±0.50%

Active energy per phase and total

±0.40%

Active energy of fundamental frequency per phase and total

±0.50%

Active energy of harmonics per phase and total

±0.80%

Reactive energy per phase and total

±0.50%

Per phase and arithmetic total

±0.50%

Vector sum

±0.80%

Electrical isolation

Channel isolated from bus
Channel not isolated from channel

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Not permitted

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

See section "Derating".

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB32 separately.
Order 1x bus module X20BM32 separately.

Pitch

25+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20AP3121”

Your email address will not be published. Required fields are marked *