Fast delivery within 72 Hours

B&R X20AI2437

2 analog current measurement inputsElectrically isolated analog channelsElectrically isolated sensor supplies16-bit digital converter resolutionNetTime timestamp: Moment of measurement…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

2 analog current measurement inputsElectrically isolated analog channelsElectrically isolated sensor supplies16-bit digital converter resolutionNetTime timestamp: Moment of measurement

The module is equipped with 2 current measurement inputs with 16-bit digital converter resolution.Each current measurement input has its own sensor supply. The two channels with their respective sensor supplies are electrically isolated from each other. The user can select between the two measurement ranges 4 to 20 mA and 0 to 25 mA.

Specification

I/O module

2 analog inputs 4 to 20 mA or 0 to 25 mA

B&R ID code

0xB784

Status indicators

I/O function per channel, operating state, module status, sensor power supply per channel

Module run/error

Yes, using LED status indicator and software

Inputs

Yes, using LED status indicator and software

Sensor power supply

Yes, using LED status indicator and software

Bus

0.05 W

Internal I/O

1.15 W

Additional power dissipation caused by actuators (resistive) [W]

CE

Yes

UKCA

Yes

CRA (Cyber Resilience Act)

In preparation

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

DNV

Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)

CCS

Yes

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33B
Temperature: 5 – 55°C
Vibration: 4 g
EMC: Bridge and open deck

KC

Yes

Input

4 to 20 mA or 0 to 25 mA configurable using software

Input type

Differential input

Digital converter resolution

16-bit

Data output rate

4.7 to 960 samples per second, configurable using software

Output format

INT

4 to 20 mA

0.0007 %/°C

0 to 25 mA

0.0002 %/°C

0 to 25000 µA

INT 0x0000 – 0x61A8 / 1 LSB = 0x0001 = 1000 nA

Load

I_IN ≥ 0.1 mA: R < 8000 Ω
I_IN ≥ 1 mA: R < 1100 Ω
I_IN ≥ 4 mA: R < 510 Ω

Input protection

Up to 30 VDC, reverse polarity protection (max. 0.1 A)

Open-circuit detection

Yes, using software

Permissible input signal

0 to 25 mA

Output of digital value during overload

Configurable

Conversion procedure

Sigma-delta

DC

80 dB

50 Hz

Depends on the sampling rate: e.g. >130 dB for 50 samples per second

Common-mode range

0 to 7 V

Nonlinearity

<0.003%

Hardware

First-order low-pass filter / cutoff frequency 2.5 kHz

Software

Sinc4 filter

Channel - Channel

1000 VAC

Channel - Bus

1000 VAC

Channel - Ground

1000 VAC

Power consumption

0.75 W per channel

Nominal voltage

25 V ±2%

Nominal output current

Max. 30 mA

Short-circuit proof

Yes, continuous

Up to 100 kHz

≤2.2 mV

Up to 1 MHz

≤22 mV

Higher

≤100 mV

Typical

<50 mA

Maximum

60 mA

Behavior on short circuit

Current limiting

Electrical isolation

Channel isolated from channel and bus
Sensor power supply isolated from sensor power supply
Sensor power supply not isolated from channel

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

5 to 95%, non-condensing

Note

Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.

Pitch

12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20AI2437”

Your email address will not be published. Required fields are marked *