400 to 500 VAC wide-range input2-phase and 3-phase operationReliable supply even if one phase fails in 3-phase operationHigh dielectric strengthCan be connected in parallel for increased capacity and redundancyReliable operation due to long power failure bypass function under full load and high MTBF (>500,000 h)International certification packageWide temperature range from -25 to 70°CClosed metal housing
24 VDC power supply, 3-phase, 10 A, input 400 to 500 VAC, wide range, top-hat rail installation
Specification
| Status display | Green LED (DC OK), threshold value Uout = 21.5 V | 
|---|---|
| Input - Output | 4 kV AC (type test) | 
| Input - Ground | 2 kV AC (type test) | 
| Output - Ground | 500 VDC (routine test) | 
| Connection type | Screw terminal | 
| Wire end sleeves | Flexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950 | 
| Flexible | 0.2 to 2.5 mm² / 16 to 12 AWG | 
| Inflexible | 0.2 to 2.5 mm² / 16 to 12 AWG | 
| Wire stripping length | 9 mm (input/output) | 
| CE | Yes | 
| UKCA | Yes | 
| CRA (Cyber Resilience Act) | Evaluation ongoing | 
| UL | cULus E123528 | 
| Nominal input voltage | 2/3x 400 to 500 VAC | 
| Input voltage | 3x 320 to 575 VAC, 45 to 65 Hz | 
| Input current | 3x 0.6 A (400 VAC) | 
| Inrush current limiting | <15 A | 
| I2t | 0.2 A2s | 
| Power failure bypass | >20 ms (400 VAC) | 
| Switch-on time | <1 s (typical) | 
| Power factor (cos φ) | 0.59 | 
| Leakage current to PE | <3.5 mA | 
| Protective circuit | Transient surge protection with varistor | 
| Required line fuse for device and line protection | 2/3x 6 A (characteristic B) | 
| Nominal voltage | 24 VDC ±1% | 
| Output power | 240 W | 
| Setting range for output voltage | 22.5 to 29.5 VDC | 
| -25 to 55°C | 10.0 A | 
| >55°C | Derating: 2.5% per °C | 
| Current limiting | Approx. 15 A | 
| Control deviation | <1% (static load change 10 to 90%) | 
| Rise time | <2 ms (UOUT (10 to 90%)) | 
| Residual ripple | <10 mVSS | 
| Switching peaks | <30 mVSS | 
| Can be connected in parallel | Yes, to establish redundancy and increase capacity | 
| Can be connected in series | No | 
| Max. capacitive load | Unlimited | 
| Protection against internal overvoltages | Yes, limited to <35 VDC | 
| Protective functions | Output protected against continuous short circuit, open circuit and overload | 
| Power back immunity | Max. 35 VDC | 
| Output noise suppression | Device complies with EN 55011 (class B) | 
| Efficiency | >88.5% | 
| MTBF | >500,000 h, per IEC 61709 (SN 29500) | 
| Rated load | Max. 34 W | 
| No-load operation | Max. 7.5 W | 
| Horizontal | Yes | 
| Vertical | No | 
| Maximum | 4000 m | 
| Ventilation/Cooling | Normal convection, no fan required | 
| Degree of protection per EN 60529 | IP20 | 
| Protection class | I, with PE connection | 
| Operation | 30 g in each direction, per IEC 60068-2-27 | 
| Storage | -40 to 85°C | 
| Transport | -40 to 85°C | 
| Pollution degree | 2, per EN 50178 | 
| Climate category | 3K3, per EN 60721 | 
| Material | Steel sheet, galvanized | 
| Installation | Easy top-hat rail installation (NS 35 rails, EN 60715) | 
| Width | 60 mm | 
| Height | 130 mm | 
| Depth | 152.5 mm | 
| Weight | 1100 g | 
 
	 
	 
				 
				
 
		 
		 
		 
		 
		 
		 
		
Reviews