Fast delivery within 72 Hours
B&R 0PS1040.0
100 to 240 VAC wide-range inputPower boost for reliable startup of demanding loads (up to 5 A)Can be connected in parallel for increased capacity and redundancyActive DC OK switch outputReliable opera…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
100 to 240 VAC wide-range inputPower boost for reliable startup of demanding loads (up to 5 A)Can be connected in parallel for increased capacity and redundancyActive DC OK switch outputReliable operation due to long power failure bypass function under full load and high MTBF (>500,000 h)International certification packageWide temperature range from -25 to 70°CExtra slender design
24 VDC power supply, 1-phase, 4 A, input 100 to 240 VAC, wide range, top-hat rail installation
Specification
| Status display | Green LED (DC OK), threshold value Uout = 21.5 V |
|---|---|
| Input - Output | 3 kV AC (type test) 3 kV AC (routine test) |
| Active DC OK switch output | 24 V, 20 mA |
| Connection type | Screw terminal |
| Wire end sleeves | Flexible cables require wire end sleeves in order to fulfill EN 62368 / UL 60950 |
| Flexible | 0.2 to 2.5 mm² / 24 to 12 AWG |
| Inflexible | 0.2 to 2.5 mm² / 24 to 12 AWG |
| Wire stripping length | 7 mm (input/output) |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | Evaluation ongoing |
| UL | cULus E123528 Industrial control equipment |
| Nominal input voltage | 100 to 240 VAC |
| Input voltage | AC 85 to 264 V (wide range), 45 to 65 Hz DC 90 to 350 V |
| Input current | Approx. 1.3 A (120 VAC) Approx. 0.8 A (230 VAC) |
| Inrush current limiting | <20 A (typical) |
| I2t | <2.1 A2s |
| Power failure bypass | >20 ms (120 VAC) >100 ms (230 VAC) |
| Switch-on time | <0.4 s |
| Protective circuit | Transient surge protection with varistor |
| Internal fuse | 3.15 A slow-blow |
| Required line fuse for line protection | 6 A 10 A 16 A (characteristic B) |
| Nominal voltage | 24 VDC ±1% |
| Output power | 96 W |
| Setting range for output voltage | 22.5 to 28.5 VDC |
| -25 to 40°C | 5.0 A |
| 40 to 60°C | 4.0 A |
| >60°C | Derating: 2.5% per °C |
| Current limiting | Approx. 9 A (for short circuit) |
| Control deviation | <1% (static load change 10 to 90%) <3% (dynamic load change 10 to 90%) <0.1% (input voltage change ±10%) |
| Rise time | 0.3 ms (UOUT (10 to 90%)) |
| Residual ripple | <100 mVpp (at nominal values) |
| Switching peaks | <100 mVSS (at nominal values) |
| Can be connected in parallel | Yes, to establish redundancy and increase capacity |
| Can be connected in series | Yes |
| Max. capacitive load | Unlimited |
| Protection against internal overvoltages | Yes, limited to approximately 35 VDC |
| Protective functions | Output protected against continuous short circuit, open circuit and overload |
| Power back immunity | Max. 35 VDC |
| Output noise suppression | Device complies with EN 55011 (class B) |
| Efficiency | >88% (at 230 VAC and nominal values) |
| MTBF | >500,000 h, per IEC 61709 (SN 29500) |
| Rated load | Max. 12 W |
| No-load operation | Max. 2.5 W |
| Horizontal | Yes |
| Vertical | No |
| Maximum | 3000 m |
| Ventilation/Cooling | Normal convection, no fan required |
| Degree of protection per EN 60529 | IP20 |
| Protection class | ΙΙ (in closed control cabinet) |
| Operation | 30 g in all directions, per IEC 68-2-27 |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Pollution degree | 2, per EN 50178 |
| Climate category | 3K3, per EN 60721 |
| Material | Polyamide PA, color green |
| Installation | Easy top-hat rail installation (NS 35 rails, EN 60715) |
| Width | 67.5 mm |
| Height | 99 mm |
| Depth | 114.5 mm |
| Weight | 400 g |

Reviews
Clear filtersThere are no reviews yet.